B22

The following table lists holding registers for the “D” Group Monitor Functions.

Appendix B

List of Holding Registers

 

Func.

Name

R/W

Description

 

Network Data

 

 

Code

Reg.

 

Range

Res.

 

 

 

 

 

 

 

 

D001

Output frequency

R

Real-time display of output

1002h

 

0 to 4000

0.1 Hz

 

 

 

monitor

 

frequency to motor, from 0.0 to

 

 

 

 

 

 

 

 

 

400.0 Hz

 

 

 

 

 

 

D002

Output current

R

Filtered display of output

1003h

 

0 to 2000

0.1%

 

 

 

monitor *1

 

current to motor (100 ms

 

 

 

 

 

 

 

 

 

internal filter time constant),

 

 

 

 

 

 

 

 

 

range is 0 to 200% of inverter

 

 

 

 

 

 

 

 

 

rated current

 

 

 

 

 

 

D003

Rotation direction

R

Three different indications:

1004h

 

0,1,2

 

 

 

monitor

 

00...Stop

 

 

 

 

 

 

 

 

 

01...Forward

 

 

 

 

 

 

 

 

 

02...Reverse

 

 

 

 

 

 

D004

Process Variable (PV),

R

Displays the scaled PID process

1005h

 

0 to

0.00%

 

 

(high)

PID feedback monitor

 

variable (feedback) value (A075

 

 

999900

times

 

 

D004

 

R

is scale factor), range is 0.00 to

1006h

 

 

const.

 

 

(low)

 

 

9999.00

 

 

 

 

 

 

D005

Intelligent input

R

Displays the state of the

1007h

 

0 to 63

 

 

 

terminal status

 

intelligent input terminals [x],

 

 

 

 

 

 

 

 

 

Bit 0 = [1] to Bit 4 = [5]

 

 

 

 

 

 

D006

Intelligent output

R

Displays the state of the

1008h

 

0 to 7

 

 

 

terminal status

 

intelligent output terminals [x],

 

 

 

 

 

 

 

 

 

Bit 0 = [11], Bit 1 = (Don’t Care),

 

 

 

 

 

 

 

 

 

Bit 2 = [AL]

 

 

 

 

 

 

D007

Scaled output

R

Displays the output frequency

1009h

 

0 to

0.01 Hz

 

 

(high)

frequency monitor

 

scaled by the constant in B086.

 

 

3996000

times

 

 

D007

 

R

Decimal point indicates range:

100Ah

 

 

const.

 

 

(low)

 

 

0.00 to 39960.00

 

 

 

 

 

 

D013

Output voltage

R

Voltage of output to motor, range

100Ch

 

0 to

0.01%

 

 

 

monitor

 

is 0.00 to 200.00%

 

 

20000

 

 

 

D016

Cumulative operation

R

Displays total time the inverter

100Eh

 

0 to

1 hour

 

 

(high)

RUN time monitor

 

has been in RUN mode in hours.

 

 

999999

 

 

 

D016

 

R

Range is 0 to 999999

100Fh

 

 

 

 

 

(low)

 

 

 

 

 

 

 

 

 

D017

Cumulative power-on

R

Displays total time the inverter

1010h

 

0 to

1 hour

 

 

(high)

time monitor

 

has been in RUN mode in hours.

 

 

999999

 

 

 

D017

 

R

Range is 0 to 999999

1011h

 

 

 

 

 

(low)

 

 

 

 

 

 

 

 

 

D018

Fin temperature

R

Display the Fin temperature in

116Ah

 

0 to 2000

0.1°C

 

 

 

monitor

 

0.0~200.0°C

 

 

 

 

 

 

D080

Trip counter

R

Number of trip events, range is 0

0011h

 

0 to 65535

1 trip

 

 

 

 

 

to 65535

 

 

 

event

 

 

D102

DC voltage monitor

R

Voltage of DC bus inside

116Ch

 

0 to 9999

0.1 V

 

 

 

 

 

inverter,Range is 0.0 to 999.9

 

 

 

 

 

 

D104

Electronic thermal

R

Accumulated value of electronic

116Dh

 

0 to 1000

0.1 %

 

 

 

monitor

 

thermal detection, range is from

 

 

 

 

 

 

 

 

 

0.0 to 100.0

 

 

 

 

 

Note 1: Assume that the inverter current rating is 1000 (for D002).