363

Output Logic and Timing

Logic Output Function – The inverter has a built-in logic output feature. You can select any two of the other nine intelligent output options for internal inputs. Then, configure the logic function to apply the logical AND, OR, or XOR (exclusive OR) operates as desired to the two inputs. The terminal symbol for the new output is [LOG]. Use C021, or C026 to route the logical result to terminal [11] or the relay terminals.

Drive Parameters

Intelligent outputs used as internal inputs:

RUN, FA1, FA2, OL, OD, AL, Dc, FBV, NDc, ODc,

LOC

RUN, FA1, FA2,

OL, OD, AL, Dc,

FBV, NDc, ODc,

LOC

C141

Input A

C142

Input B

Logic function AND, OR, XOR

C021

11

C026

AL1

AL0

AL2

Configuring

The following table shows all four possible input combinations with each of the three available logic operations.

 

 

 

Input Status

 

[LOG] Output State

 

 

 

 

 

 

 

 

 

 

 

A

B

 

AND

 

OR

 

XOR

 

 

 

 

 

 

 

 

 

 

 

0

0

 

0

 

0

 

0

 

 

 

 

 

 

 

 

 

 

 

0

1

 

0

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

1

0

 

0

 

1

 

1

 

 

 

 

 

 

 

 

 

 

 

1

1

 

1

 

1

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“C” Function

 

 

 

Run

Defaults

 

 

Func.

 

Name /

 

 

 

 

Description

 

Mode -FE -FU

Units

 

 

Code

 

SRW Display

 

 

 

Edit (EU)

 

(USA)

 

 

C141

Input A select for logic

11 programmable functions

 

00

 

00

 

 

 

 

output

 

 

 

 

available for logic (discrete)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outputs

 

 

 

 

 

 

 

 

 

 

 

 

LogicOut1

RUN

 

 

 

 

 

 

 

 

 

 

 

 

00RUN 01FA1

02FA2

 

 

 

 

 

 

 

C142

Input B select for logic

 

01

 

01

 

 

03OL

04OD

05AL

 

 

 

 

 

 

output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06Dc

07FBV 08NDc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LogicOut2

FA1

09LOG 10ODc 43LOC

 

 

 

 

 

 

 

C143

Logic function select

Applies a logic function to calculate

 

00

 

00

 

 

 

 

 

 

 

 

 

[LOG] output state,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00[LOG] = A AND B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01[LOG] = A OR B

 

 

 

 

 

 

 

 

 

 

LogicOPE

AND

02[LOG] = A XOR B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 137
Image 137
Hitachi X200 Series instruction manual 63, Output Logic and Timing, LogicOut1, LogicOut2, LogicOPE