Hitachi X200 Series Forward Run/Stop and Reverse Run/Stop Commands, Valid for inputs C001~C005

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 150
Image 150

411

Forward Run/Stop and Reverse Run/Stop Commands:

When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low).

Option

Terminal

Function Name

State

Description

Code

Symbol

 

 

 

00

FW

Forward Run/Stop

ON

Inverter is in Run Mode, motor runs forward

 

 

 

OFF

Inverter is in Stop Mode, motor stops

01

RV

Reverse Run/Stop

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

OFF

Inverter is in Stop Mode, motor stops

Valid for inputs:

C001~C005

Required settings

A002 = 01

Notes:

 

When the Forward Run and Reverse Run commands are active at the same time, the inverter enters the Stop Mode.

When a terminal associated with either [FW] or [RV] function is configured for normally closed, the motor starts rotation when that terminal is disconnected or otherwise has no input voltage.

Example (default input configuration shown

– see page 3-49)

 

 

 

RV

FW

 

 

 

5

4

3

2

1

L

PLC

P24

See I/O specs on page 4-6.

NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] and [RV] input terminal operation.

WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.

Operations and Monitoring

Page 150
Image 150
Hitachi X200 Series Forward Run/Stop and Reverse Run/Stop Commands, Terminal Function Name State Description, A002 =