314

Configuring Drive Parameters

 

 

 

“A” Function

Run

Defaults

 

Func.

Name /

Description

Mode -FE -FU

Units

 

Code

SRW Display

Edit (EU)

(USA)

 

A005

[AT] selection

Five options; select codes:

02

02

 

 

 

02Select between [O] and

 

 

 

 

 

 

integrated POT at [AT]

 

 

 

 

 

 

03Select between [OI] and

 

 

 

 

 

 

integrated POT at [AT]

 

 

 

 

 

 

04Only [O] input active

 

 

 

 

 

 

05Only [OI] input active

 

 

 

 

AT-Slct

O/VR

 

 

 

 

A011

O-L input active range start

The output frequency

0.0

0.0

Hz

 

frequency

 

corresponding to the analog input

 

 

 

 

 

 

range starting point,

 

 

 

 

O-EXS

0000.0Hz

range is 0.0 to 400.0

 

 

 

A012

O-L input active range end

The output frequency

0.0

0.0

Hz

 

frequency

 

corresponding to the analog input

 

 

 

 

 

 

range ending point,

 

 

 

 

O-EXE

0000.0Hz

range is 0.0 to 400.0

 

 

 

A013

O-L input active range start

The starting point (offset) for the

0.

0.

%

 

voltage

 

active analog input range,

 

 

 

 

 

 

range is 0. to 100.

 

 

 

 

O-EX%S

00000%

 

 

 

A014

O-L input active range end

The ending point (offset) for the

100.

100.

%

 

voltage

 

active analog input range,

 

 

 

 

 

 

range is 0. to 100.

 

 

 

 

O-EX%E

00000%

 

 

 

A015

O-L input start frequency

Two options; select codes:

01

01

 

enable

 

00Use offset (A011 value)

 

 

 

 

O-LVL

0Hz

01Use 0Hz

 

 

 

A016

External frequency filter time

Range n = 1 to 17, where n =

8.

8.

Sam-

 

constant

 

number of samples for avg.

 

 

ples

 

 

 

 

 

 

 

 

F-SAMP

00008

 

 

 

 

Page 88
Image 88
Hitachi X200 Series instruction manual Exs, Exe, Ex%S, Ex%E, Lvl, Samp