364

Output Signal ON/OFF Delay Function – Intelligent outputs including terminals [11] and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor inverter output signals to meet timing requirements of certain external devices.

 

 

“C” Function

Run

 

Defaults

 

Func.

Name /

Description

Mode -FE -FU

Units

 

Code

SRW Display

Edit

(EU)

(USA)

 

C144

Terminal [11] ON delay

Range is 0.0 to 100.0 sec.

 

0.0

0.0

sec.

 

DLAY 11

000.0s

 

 

 

 

C145

Terminal [11] OFF delay

Range is 0.0 to 100.0 sec.

0.0

0.0

sec.

 

 

 

 

 

 

 

 

HOLD 11

000.0s

 

 

 

 

C148

Output relay ON delay

Range is 0.0 to 100.0 sec.

0.0

0.0

sec.

 

 

 

 

 

 

 

 

DLAY RY

000.0s

 

 

 

 

C149

Output relay OFF delay

Range is 0.0 to 100.0 sec.

0.0

0.0

sec.

 

 

 

 

 

 

 

 

HOLD RY

000.0s

 

 

 

 

NOTE: If you are using the output terminal OFF delay feature (any of C145, C149 > 0.0 sec.), the [RS] (reset) terminal affects the ON-to-OFF transition slightly. Normally (with using OFF delays), the [RS] input causes the motor output and the logic outputs to turn OFF together, immediately. However, when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 1 sec. period (approximate) before turning OFF.

Configuring Drive Parameters

Page 138
Image 138
Hitachi X200 Series instruction manual 64, Dlay RY, Hold RY