Hitachi X200 Series instruction manual Remote Control Data Clears the Up/Down frequency memory

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 167
Image 167

428

It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals through a power loss. Parameter C101 enables/disables the memory. If disabled, the inverter retains the last frequency before an UP/DWN adjustment. Use the [UDC] terminal to clear the memory and return to the original set output frequency.

Option

Terminal

Function Name

 

State

 

 

Description

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

UP

Remote Control UP

 

ON

Accelerates (increases output frequency) motor

 

 

Function (motorized

 

 

from current frequency

 

 

speed pot.)

 

OFF

Output to motor operates normally

28

DWN

Remote Control

 

ON

Decelerates (increases output frequency) motor

 

 

DOWN Function

 

 

from current frequency

 

 

(motorized speed pot.)

 

OFF

Output to motor operates normally

29

UDC

Remote Control Data

 

ON

Clears the Up/Down frequency memory

 

 

Clear

 

OFF

No effect on Up/Down memory

Valid for inputs:

C001~C005

 

Example (default input configuration shown—see

Required settings

A001 = 02

 

page 3–49):

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

DWN

UP

 

 

 

 

 

5

4

3

2

1

L

PCS

P24

 

This feature is available only when the frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command source is programmed for operator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control. Confirm A001 is set to 02.

 

 

 

 

 

 

 

 

 

 

 

 

 

This function is not available when [JG] is in use.

 

 

 

 

 

 

 

 

 

 

 

 

The range of output frequency is 0 Hz to the value

 

 

 

 

 

 

 

 

 

 

 

 

in A004 (maximum frequency setting).

 

See I/O specs on page 4–6.

The minimum ON time of [UP] and [DWN] is 50 ms.

This setting modifies the inverter speed from using F001 output frequency setting as a starting point.

Page 167
Image 167
Hitachi X200 Series instruction manual Remote Control Data Clears the Up/Down frequency memory