64

Troubleshooting and Maintenance

Symptom/condition

Probable Cause

Solution

 

 

If using the analog input, is the

Check the wiring.

 

 

current or voltage at [O] or [OI]?

Check the potentiometer or

 

 

 

signal generating device.

 

 

Is the load too heavy?

Reduce the load.

The motor speed will not

 

Heavy loads activate the

reach the target frequency

 

overload restriction feature

(desired speed).

 

(reduces output as needed).

 

 

Is the inverter internally limiting

Check max frequency setting

 

 

the output frequency?

(A004)

 

 

 

Check frequency upper limit

 

 

 

setting (A061)

 

 

Is the load fluctuation too great?

Increase the motor capacity

 

 

Is the supply voltage unstable?

(both inverter and motor).

The rotation is unstable

Is the problem occurring at a

Fix power supply problem.

particular frequency?

Change the output frequency

 

 

 

slightly, or use the jump

 

 

 

frequency setting to skip the

 

 

 

problem frequency.

 

 

Is the maximum frequency setting

Verify the V/f settings match

The RPM of the motor does

A004 correct?

motor specifications.

not match the inverter

Does the monitor function D001

Make sure all scaling (such as

output frequency setting.

display the expected output

A011 to A014) is properly set.

 

 

frequency?

 

 

 

Was power turned OFF after a

Edit the data and press the

 

 

parameter edit but before pressing

Store key once.

 

No download has

the Store key?

 

 

Edits to data are permanently

Wait six seconds or more

Inverter

occurred

stored at power down. Was the time

before turning power OFF

 

data us not

 

from power OFF to power ON less

after editing data.

correct

 

than six seconds?

 

 

The download

Was the power turned OFF within

Copy the data to the inverter

 

to the inverter

six seconds after the display

again, and keep power ON for

 

was attempted

changed from REMT to INV?

six seconds or more after

 

 

 

copying.

A

True for

Is the inverter in Run Mode? Some

Put inverter in Stop Mode

parameter

parameters cannot be edited during

(press the Stop/reset key).

will not

certain

Run Mode.

Then edit the parameter.

change

parameters

 

 

after an

 

 

 

True for all

If you’re using the [SFT] intelligent

Change the state of the SFT

edit

parameters

input (software lock function)—is

input, and check the B031

(reverts to

 

the [SFT] input ON?

parameter (SFT mode).

old

 

 

 

 

setting).

 

 

 

Page 207
Image 207
Hitachi X200 Series instruction manual Reduces output as needed