37

 

 

“D” Function

 

Run

 

Func.

 

Name /

 

Description

Mode

Units

Code

SRW Display

 

Edit

 

 

 

 

D007

Scaled output frequency

Displays

the output frequency

Hz times

 

monitor

 

scaled by the constant in B086.

 

constant

 

 

 

Decimal point indicates range:

 

 

 

 

 

XX.XX

0.00 to 99.99

 

 

 

 

 

XXX.X

100.0 to 999.9

 

 

 

 

 

XXXX.

1000. to 9999.

 

 

 

 

 

XXXX

1000 to 9999

 

 

 

F-Cnv

00000.00

 

(x10=10000 to 99999)

 

 

D013

Output voltage monitor

Voltage of output to motor,

V

 

 

 

Range is 0.0 to 600.0V

 

 

 

Vout

00000V

 

 

 

 

D016

Cumulative operation

Displays total time the inverter has

hours

 

RUN time monitor

been in RUN mode in hours.

 

 

 

 

 

Range is 0 to 9999 / 1000 to 9999 /

 

 

 

RUN

0000000hr

100 to 999 (10,000 to 99,900)

 

 

D017

Cumulative power-on time

Displays total time the inverter has

hours

 

monitor

 

been powered up in hours.

 

 

 

 

 

Range is 0 to 9999 / 1000 to 9999 /

 

 

 

RUN

0000000hr

 

 

 

100 to 999 (10,000 to 99,900)

 

 

D018

Cooling

Fin temperature

Temperature of the cooling fin.

°C

 

monitor

 

(0.0~200)

 

 

 

 

TH-Fin

0000.0 C

 

 

 

 

Trip Event and History Monitoring

The trip event and history monitoring features lets you cycle through related information using the keypad. See “Monitoring Trip Events, History, & Conditions” on page 6-5 for more details.

 

 

 

“D” Function

Run

 

 

 

Func.

Name /

Description

Mode

Units

 

 

Code

SRW Display

Edit

 

 

 

 

 

 

 

D080

Trip counter

 

Number of trip events,

events

 

 

 

 

 

Range is 0. to 9999

 

 

 

 

 

ERR CNT

00000

 

 

 

 

 

D081

Trip monitor 1

 

Displays trip event information:

 

 

 

 

 

 

Error code

 

 

 

 

 

ERR1

########

Output freq. at trip point

 

 

 

 

D082

Trip monitor 2

 

Motor current at trip point

 

 

 

 

 

DC bus voltage at trip point

 

 

 

 

 

 

 

Cumulative inverter operation

 

 

 

 

 

ERR2

########

 

 

 

 

 

 

 

time at trip point

 

 

 

 

D083

Trip monitor 3

 

 

 

 

Cumulative power-ON time at

 

 

 

 

 

 

 

 

 

 

ERR3

########

trip point

 

 

 

 

D102

DC bus voltage monitor

Voltage of DC bus inside inverter,,

V

 

 

 

Vpn

0000.0Vdc

Range is 0.0 to 999.9

 

 

 

 

D104

Electronic thermal monitor

Accumulated value of electronic

%

 

 

 

 

 

thermal detection, range is from 0.0

 

 

 

 

 

 

 

to 100.0

 

 

 

 

 

E-THM

0000.0%

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive Parameters

Page 81
Image 81