Potentiometer Settings

Input Range Settings – The parameters in the following table adjust the input characteristics of the integrated POT. When using the POT to command the inverter output frequency, these parameters adjust the starting and ending ranges for the POT, as well as the output frequency range.

 

 

“A” Function

Run

Defaults

Func.

Name /

Description

Mode -FE -FU

Units

Code

SRW Display

Edit (EU)

 

(USA)

A151

POT active range start

The output frequency

 

0.0

 

0.0

Hz

 

frequency

 

corresponding to the POT range

 

 

 

 

 

 

 

 

starting point,

 

 

 

 

 

 

POT-EXS

0000.0Hz

range is 0.0 to 400.0 Hz

 

 

 

 

 

A152

POT input active range end

The output frequency

 

0.0

 

0.0

Hz

 

frequency

 

corresponding to the POT range

 

 

 

 

 

 

 

 

ending point,

 

 

 

 

 

 

POT-EXE

0000.0Hz

range is 0.0 to 400.0 Hz

 

 

 

 

 

A153

POT input active range start

The starting point (offset) for the

 

0.

 

0.

%

 

 

 

POT range,

 

 

 

 

 

 

POT-EX%S

00000%

range is 0. to 100.%

 

 

 

 

 

A154

POT input active range end

The ending point (offset) for the

 

100.

 

100.

%

 

 

 

POT range,

 

 

 

 

 

 

POT-EX%E

00000%

range is 0. to 100.%

 

 

 

 

 

A155

POT input start frequency

Two options; select codes:

 

01

 

01

 

enable

 

00Use offset (A151 value)

 

 

 

 

 

 

 

 

01Use 0Hz

 

 

 

 

 

 

POT-LVL

0Hz

 

 

 

 

 

 

Max frequency

 

A152

 

 

 

 

A015=00

 

 

A151

 

A015=01

 

 

 

 

0

 

 

%

 

 

 

0%

A153

A154

100%

Counterclockwise

 

Clockwise

Input scale

Configuring Drive Parameters

Page 105
Image 105