Hitachi X200 Series instruction manual Sinking Inputs, External Supply

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 149
Image 149

410

Operations and Monitoring

The two diagrams below show input wiring circuits using an external supply. If using the “Sinking Inputs, External Supply” in below wiring diagram, be sure to remove the short bar, and use a diode (*) with the external supply. This will prevent a power supply contention in case the short bar is accidentally placed in the incorrect position. For the “Sourcing Inputs, External Supply”, please connect the short bar as drawn in the diagram below.

Sinking Inputs, External Supply

 

 

 

 

 

Short bar = Removed

 

 

 

X200

 

 

 

 

 

P24

 

Field device

 

 

 

24V

 

 

 

 

 

*

24V

*

PLC

Input common

+

+

24V

 

+

 

 

-

 

 

 

 

-

 

 

-

 

 

 

 

GND

 

Logic GND

L

 

 

 

 

 

 

 

 

 

1

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

 

 

 

circuits

 

 

5

 

 

5

 

 

 

 

 

 

 

 

 

 

 

Input switches

 

 

 

Open collector outputs,

* Note: If the external power supply to GND is (optionally)

connected to [L], then install the above diode.

 

NPN transistors

 

 

 

 

 

Sourcing Inputs, External Supply

Short bar = [PLC] – [L]

 

 

Short bar

 

PNP transistor

 

 

sousing outputs

 

P24

 

 

24V

Field device

 

+

PLC

 

 

 

 

-

 

 

 

 

L

 

 

1

1

 

 

 

 

 

5

5

 

 

 

+

24V

Input switches

 

-

 

GND

 

 

 

 

X200

Input common

24V

+

 

 

-

Input circuits

Page 149
Image 149
Hitachi X200 Series instruction manual Sinking Inputs, External Supply