Hitachi X200 Series instruction manual Fine Tuning Functions, Group Parameters, Func Name =10

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 272
Image 272

C6

Fine Tuning Functions

Appendix C

 

 

“B” Group Parameters

Default Setting

B031

User

 

 

Func.

 

-FE

-FU

 

 

Name

=10

Setting

 

 

Code

(EU)

(USA)

 

 

 

 

 

 

 

B001

Selection of automatic restart mode

00

00

9

 

 

 

B002

Allowable under-voltage power failure

1.0

1.0

9

 

 

 

 

time

 

 

 

 

 

 

B003

Retry wait time before motor restart

1.0

1.0

9

 

 

 

B004

Instantaneous power failure / under-

00

00

9

 

 

 

 

voltage trip alarm enable

 

 

 

 

 

 

B005

Number of restarts on power failure /

00

00

9

 

 

 

 

under-voltage trip events

 

 

 

 

 

 

B011

Start freq to be used in case of freq

00

00

 

 

 

 

 

matching restart

 

 

 

 

 

 

B012

Level of electronic thermal setting

Rated current for

9

 

 

 

 

 

each inverter

 

 

 

 

B212

Level of electronic thermal setting, 2nd

Rated current for

9

 

 

 

 

motor

each inverter

 

 

 

 

B013

Electronic thermal characteristic

01

01

9

 

 

 

B213

Electronic thermal characteristic, 2nd

01

01

9

 

 

 

 

motor

 

 

 

 

 

 

B021

Overload restriction operation mode

01

01

9

 

 

 

B221

Overload restriction operation mode,

01

01

9

 

 

 

 

2nd motor

 

 

 

 

 

 

B022

Overload restriction level setting

Rated current x 1.5

9

 

 

 

B222

Overload restriction operation mode,

Rated current x 1.5

9

 

 

 

 

2nd motor

 

 

 

 

 

 

B023

Deceleration rate at overload restriction

1.0

30.0

9

 

 

 

B223

Overload restriction operation mode,

1.0

30.0

9

 

 

 

 

2nd motor

 

 

 

 

 

 

B028

Source of overload restriction selection

00

00

 

 

 

 

B228

Source of overload restriction selection,

00

00

9

 

 

 

 

2nd motor

 

 

 

 

 

 

B029

Deceleration rate of frequency matching

0.5

0.5

 

 

 

 

 

restart setting

 

 

 

 

 

 

B030

Current level of frequency matching

Rated

current

 

 

 

 

 

restart setting

 

 

 

 

 

 

B031

Software lock mode selection

01

01

9

 

 

 

B050

Selection of the non stop operation

00

00

 

 

 

 

B051

Non stop operation start voltage setting

0.0

0.0

 

 

 

 

B052

OV-LAD Stop level of non stop operation

0.0

0.0

 

 

 

 

 

setting

 

 

 

 

 

 

B053

Deceleration time of non stop operation

1.0

1.0

 

 

 

 

 

setting

 

 

 

 

 

 

B054

Frequency width of quick deceleration

0.0

0.0

 

 

 

 

 

setting

 

 

 

 

 

 

B055

DC bus AVR P-gain

0.2

0.2

 

 

 

 

B056

DC bus AVR I-time

0.2

0.2

 

 

 

 

B057

DC bus AVR D-time

0.0

0.0

 

 

 

 

 

 

 

 

 

 

 