Hitachi X200 Series 57, Low Load Detection Parameters, LOC Mode CRT, Loc Lvl, 02.60A

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 131
Image 131

Drive

Low Load Detection Parameters

The following parameters work in

 

 

conjunction with the intelligent output

Output

function, when configured. The output

current

mode parameter (C038) sets the mode of

 

 

 

C039

the detection at which the low load

 

 

 

detection signal [LOC] turns ON. Three

 

 

kinds of modes can be selected. The

 

 

detection level parameter (C039) is to set

0

the level of the low load.

 

[LOC]

This function is for generating an early

 

output

1

warning logic output, without causing

0

either a trip event or a restriction of the

 

 

motor current (those effects are available

 

 

on other functions).

 

 

357

t

t

Configuring Parameters

 

 

 

“C” Function

Run

Defaults

 

Func.

Name /

Description

Mode -FE -FU

Units

 

Code

SRW Display

Edit (EU)

 

(USA)

 

C038

Output mode of low load

Three option codes:

 

01

 

01

 

 

detection signal

00Disabled

 

 

 

 

 

 

 

 

 

01During acceleration, deceleration

 

 

 

 

 

 

 

 

 

and constant speed

 

 

 

 

 

 

 

 

 

02During constant speed only

 

 

 

 

 

 

 

LOC MODE

CRT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C039

Low load detection level

Set the level of low load detection,

 

INV

 

INV

A

 

 

 

 

range is 0.0 to 2.0*inverter rated

 

rated

rated

 

 

 

LOC LVL

02.60A

current

 

curr.

 

curr.

 