Hitachi X200 Series instruction manual Force Terminal Mode, Inverter Ready

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 170
Image 170
F-TM

431

Force Terminal Mode

The purpose of this intelligent input is to allow a device to force the inverter to allow control of the following two parameters via the control terminals:

A001 - Frequency source setting (01 = control terminals [FW] and [RV]

A002 - Run command source setting (01 = control terminals [O] or [OI]

Some applications will require one or both settings above to use a source other than the terminals. You may prefer to normally use the inverter’s keypad and potentiometer, or to use the ModBus network for control, for example. However, an external device can turn ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency source and Run command) via control terminals. When the [F-TM] input is OFF, then the inverter uses the regular sources specified by A001 and A002 again.

Option

Terminal

Function Name

State

Description

Code

Symbol

 

 

 

51

F-TM

Force Terminal

ON

Forces A001=01 (frequency source setting =

 

 

Mode

 

control terminal), and A002=01(Run command

 

 

 

 

source setting = control terminal)

 

 

 

OFF

Inverter applies the user setting for A001 and

 

 

 

 

A002 normally

Valid for inputs:

C001~C005

Required settings

A001, A002

Notes:

When changing the [F-TM] state during Run Mode (inverter is driving the motor), the inverter will stop the motor before the new [F- TM] state takes effect.

Example (default input configuration shown—see page 3–49):

5

4

3

2

1

L

PCS

P24

See I/O specs on page 4–6.

Operations and Monitoring

Inverter Ready

The purpose of this intelligent input is to make inverter ready to start the motor immediately when the RUN command is given. When the RDY input is active, motor output terminal is active even if there is no RUN command.

Option

Terminal

Function Name

State

 

Description

Code

Symbol

 

 

 

 

 

52

RDY

Inverter Ready

ON

Inverter is ready to act immediately when the

 

 

 

 

RUN command is given.

 

 

 

OFF

Inverter performs normal start when the RUN

 

 

 

 

command is given.

 

Valid for inputs:

C001~C005

 

Example (default input configuration shown—see

Required settings

A001, A002

 

page 3–49):

RDY

Notes:

5

4

3

2

1

L

PCS

P24

See I/O specs on page 4–6.

HIGH VOLTAGE: When set RDY function ON, there will be a voltage appear at motor output terminals U, V and W even if the motor is in stop mode. So never touch the inverter power terminal even the motor is not running.

Page 170
Image 170
Hitachi X200 Series instruction manual Force Terminal Mode, Inverter Ready