39

“F” Group: Main Profile Parameters

The basic frequency (speed) profile is

Output

 

 

 

 

 

 

defined by parameters contained in the “F”

 

 

F002

 

F003

 

Group as shown to the right. The set

frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

running frequency is in Hz, but acceleration

 

F001

 

 

 

 

 

 

and deceleration are specified in the time

 

 

 

 

 

 

 

 

duration

of

the ramp

(from

zero to

 

 

0

 

 

 

 

 

maximum

frequency,

or

from

maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

frequency

to

zero).

The

motor

direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameter determines whether the keypad Run key produces a FWD or REV command.

This parameter does not affect the intelligent terminal [FW] and [REV] functions, which you configure separately.

Acceleration 1 and Deceleration 1 are the standard default accel and decel values for the main profile. Accel and decel values for an alternative profile are specified by using parameters Ax92 through Ax93. The motor direction selection (F004) determines the direction of rotation as commanded only from the keypad. This setting applies to any motor profile (1st or 2nd) in use at t particular time.

 

 

“D” Function

 

Run

 

Defaults

Func.

 

Name /

 

Description

Mode -FE -FU

Units

Code

SRW Display

 

Edit

(EU)

 

(USA)

F001

Output frequency setting

Standard default target

9

0.0

 

0.0

Hz

 

 

 

frequency that determines

 

 

 

 

 

 

 

 

constant motor speed, range is

 

 

 

 

 

 

VR

0000.0Hz

0.0 / start frequency to 400 Hz

 

 

 

 

 

F002

Acceleration (1) time setting

Standard default acceleration,

9

10.0

 

10.0

sec.

 

 

 

range is 0.01 to 3000 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACC 1

010.00s

 

 

 

 

 

 

 

F202

Acceleration (1) time setting,

Standard default acceleration,

9

10.0

 

10.0

sec.

 

2nd motor

 

2nd motor

 

 

 

 

 

 

 

 

range is 0.01 to 3000 sec.

 

 

 

 

 

 

2ACC 1

010.00s

 

 

 

 

 

F003

Deceleration (1) time setting

Standard default deceleration,

9

10.0

 

10.0

sec.

 

 

 

range is 0.01 to 3000 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEC 1

010.00s

 

 

 

 

 

 

 

F203

Deceleration (1) time setting,

Standard default deceleration,

9

10.0

 

10.0

sec.

 

2nd motor

 

2nd motor

 

 

 

 

 

 

 

 

range is 0.01 to 3000 sec.

 

 

 

 

 

 

2DEC 1

010.00s

 

 

 

 

 

F004

Cumulative power-on time

Two options; select codes:

 

00

 

00

 

monitor

 

00

Forward

 

 

 

 

 

 

DIG-RUN

FWD

01

Reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive Parameters

Page 83
Image 83
Hitachi X200 Series instruction manual Group Main Profile Parameters, Acc, Dec, Dig-Run Fwd