“A” Group: Standard Functions

Configuring Drive Parameters

The inverter provides flexibility in how you control Run/Stop operation and set the output frequency (motor speed). It has other control sources that can override the A001

/A002 settings. Parameter A001 sets the source selection for the inverter’s output frequency. Parameter A002 selects the Run command source (for FW or RV Run commands). The default settings use the input terminals for –FE (European) models, and the keypad for –FU (USA) models.

 

 

“A” Function

 

Run

 

Defaults

Func.

Name /

 

 

Description

Mode -FE -FU

Units

Code

SRW Display

 

 

Edit

(EU)

 

(USA)

A001

Frequency source setting

Five options; select codes:

 

01

 

00

 

 

 

00

Keypad potentiometer

 

 

 

 

 

 

F-COM

VR

 

 

 

 

 

 

01

Control terminal

 

 

 

 

 

A201

Frequency source setting,

02

Function F001 setting

 

01

 

00

 

2nd motor

 

03

ModBus network input

 

 

 

 

 

 

 

 

10

Calculate function output

 

 

 

 

 

 

2F-COM

VR

 

 

 

 

 

A002

Run command source setting

Three options; select codes:

 

01

 

02

 

 

 

01

Control terminal

 

 

 

 

 

 

OPE-Mode

REM

02

Run key on keypad,

 

 

 

 

 

 

 

or digital operator

 

 

 

 

 

A202

Run command source setting,

 

 

01

 

02

 

2nd motor

 

03

ModBus network input

 

 

 

 

 

 

OPE-Mode

REM

 

 

 

 

 

 

 

Frequency Source Setting – For parameter A001, the following table provides a further description of each option, and a reference to other page(s) for more information.

 

Code

Frequency Source

Refer to page(s)…

00Keypad potentiometer – The range of rotation of the knob matches the range defined by B082 (Start frequency adjustment) to A004 (Maximum frequency setting)

01Control terminal – The active analog input signal on analog terminals [O] or [OI] sets the output frequency

02Function F001 setting – The value in F001 is a constant, used for the output frequency

03ModBus network input – The network has a dedicated resister for inverter output frequency

10Calculate function output – The Calculated function has user-selectable analog input sources (A and B). the output can be the sum, difference, or product (+, -, x) of the two outputs.

2-24

4-53, 3-13, 3-28,

3-49

3-9

B-19

3-29