335

Overload Restriction

 

 

If the inverter’s output current exceeds a

Motor

 

preset current level you specify during

current

Restriction area

acceleration or constant speed, the overload

B022

 

restriction feature automatically reduces the

 

 

 

output frequency to restrict the overload.

 

 

This feature does not generate an alarm or

0

t

trip event. You can instruct the inverter to

 

 

apply overload restriction only during

 

 

constant speed, thus allowing higher

Output

 

currents for acceleration. Or, you may use

frequency

 

the same threshold for both acceleration and

 

 

constant speed.

 

 

When the inverter detects an overload, it

0

t

must decelerate the motor to reduce the

current until it s less than the threshold. You

 

B022

can choose the rate of deceleration that the

 

Parameters

 

 

inverter uses to lower the output current.

 

 

 

 

“B” Function

Run

Defaults

Func.

Name /

 

Description

Mode -FE -FU

Units

Code

SRW Display

Edit (EU)

 

(USA)

B021

Overload restriction

Select the operation mode during

 

01

 

01

 

operation mode

 

overload conditions, three

 

 

 

 

 

 

 

 

options, option codes:

 

 

 

 

 

 

OL Mode

ON

00Disabled

 

 

 

 

 

B221

Overload restriction

01Enabled for acceleration and

 

01

 

01

 

operation mode, 2nd motor

constant speed

 

 

 

 

 

 

 

 

02Enabled for constant speed

 

 

 

 

 

 

2OL Mode

ON

 

 

 

 

 

 

only

 

 

 

 

 

B022

Overload restriction level

Sets the level for overload

 

Rated

A

 

setting

 

restriction, between 20% and

 

current

 

 

OL LVL

002.40A

150% of the rated current of the

 

x 1.5

 

 

inverter, setting resolution is 1%

 

 

B222

Overload restriction level

 

Rated

A

of rated current

 

 

setting, 2nd motor

 

 

current

 

 

 

 

 

 

 

2OL LVL

002.40A

 

 

x 1.5

 

B023

Deceleration rate at overload

Sets the deceleration rate when

 

1.0

 

30.0

sec.

 

restriction

 

inverter detects overload, range

 

 

 

 

 

 

OL Cnst

0001.0s

is 0.1 to 30.0, resolution 0.1

 

 

 

 

 

B223

Deceleration rate at overload

 

 

1.0

 

30.0

sec.

 

restriction, 2nd motor

 

 

 

 

 

 

 

2OL Cnst

0001.0s

 

 

 

 

 

 

B028

Source of overload restriction

Two option codes:

 

00

 

00

 

selection

 

00set value of B022

 

 

 

 

 

 

OL L_SLCT

PARAM

01[O] input

 

 

 

 

 

B228

Source of overload restriction

Two option codes:

 

00

 

00

 

selection, 2nd motor

00set value of B222

 

 

 

 

 

 

2OL L_SLCT

PARAM

01[O] input

 

 

 

 

 

Configuring Drive

Frequency Pull-in Restart

See “Restart Mode Configuration” (B088) section on page 3-42.

Page 109