Hitachi X200 Series ModBus Data Listing, ModBus Coil List, List of Coil Numbers Name Description

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 246
Image 246

B19

ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The table legend is given below.

Coil Number - The network register address offset for the coil. The coil data is a single bit (binary) value.

Name - The functional name of the coil

R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data

Description - The meaning of each of the states of the coils

List of Coil Numbers

 

Coil

Name

R/W

Description

 

 

Number

 

 

 

 

 

 

 

0000h

(Reserved)

R

 

 

0001h

Run command

R/W

0…Stop

 

 

 

 

 

1…Run (enable when A003=03)

 

 

0002h

FW/RV command

R/W

0…RV

 

 

 

 

 

1…FW (enable when A003=03)

 

 

0003h

External trip (EXT)

R/W

0…No trip event

 

 

 

 

 

1…Trip occurred

 

 

0004h

Trip reset (RS)

R/W

0…No reset condition

 

 

 

 

 

1…Reset

 

 

0005h

(Reserved)

R

 

 

0006h

(Reserved)

R

 

 

0007h

Intelligent input terminal 1

R/W

0…OFF *1

 

 

0008h

Intelligent input terminal 2

R/W

1…ON

 

 

0009h

Intelligent input terminal 3

R/W

 

 

 

000Ah

Intelligent input terminal 4

R/W

 

 

 

000Bh

Intelligent input terminal 5

R/W

 

 

 

000Dh

(Not used)

 

 

000Eh

Run/Stop status

R

0…Stop (corresponds to D003 monitor)

 

 

 

 

 

1…Run

 

 

000Fh

FW/RV status

R

0…FW

 

 

 

 

 

1…RV

 

 

0010h

Inverter ready

R

0…Not ready

 

 

 

 

 

1…Ready

 

 

0011h

(Reserved)

R

 

 

0012h

(Reserved)

R

 

 

0013h

(Reserved)

R

 

Appendix B

Page 246
Image 246
Hitachi X200 Series instruction manual ModBus Data Listing, ModBus Coil List, List of Coil Numbers Name Description