362

Miscellaneous Functions

The following table contains miscellaneous functions not in other function groups.

 

 

“C” Function

Run

 

Defaults

Func.

Name /

 

Description

Mode -FE -FU

Units

Code

SRW Display

Edit

(EU)

 

(USA)

C091

Debug mode enable *

Displays debug parameters.

9

00

 

00

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

01Enable <Do not set>

 

 

 

 

 

 

DBG Slct

OFF

(for factory use)

 

 

 

 

 

C101

Up/Down memory mode

Controls speed setpoint for the

 

00

 

00

 

selection

 

inverter after power sycle.

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

00Clear last frequency (return to

 

 

 

 

 

 

 

 

default frequency F001)

 

 

 

 

 

 

 

 

01Keep last frequency adjusted

 

 

 

 

 

 

UP/DWN

NO-STR

by UP/DWN

 

 

 

 

 

C102

Reset selection

 

Determines response to Reset

 

00

 

00

 

 

 

input [RS].

 

 

 

 

 

 

 

 

Three option codes:

 

 

 

 

 

 

 

 

00Cancel trip state at input

 

 

 

 

 

 

 

 

signal ON transition, stops

 

 

 

 

 

 

 

 

inverter if in Run Mode

 

 

 

 

 

 

 

 

01Cancel trip state at signal

 

 

 

 

 

 

 

 

OFF transition, stops inverter

 

 

 

 

 

 

 

 

if in Run Mode

 

 

 

 

 

 

 

 

02Cancel trip state at input ON

 

 

 

 

 

 

 

 

transition, no effect if in Run

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

RS Slct

ON

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive Parameters

CAUTION: Do not change Debug mode for safety reasons. Otherwise unexpected performances may occur.