Frequency-related Functions

Frequency Limits – Upper and lower limits can be imposed on the inverter output frequency. These limits will apply regardless of the source of the speed reference. You can configure the lower frequency limit to be greater than zero as shown in the graph. The upper limiter must not exceed the rating of the motor or capability of the machinery. The maximum frequency setting (A004/A204) takes precedence over frequency upper limit (A061/A261).

Output

 

frequency

 

A061

Upper

 

 

limit

 

 

 

Settable

 

 

range

A062

Lower

 

 

limit

 

 

0

Frequency command

 

 

Configuring Drive Parameters

 

 

“A” Function

Run

Defaults

Func.

 

Name /

Description

Mode -FE -FU

Units

Code

SRW Display

Edit (EU)

 

(USA)

A061

Frequency upper limit setting

Sets a limit on output frequency

 

0.0

 

0.0

Hz

 

 

 

less than the maximum

 

 

 

 

 

 

 

 

frequency (A004).

 

 

 

 

 

 

 

 

Range is from frequency lower

 

 

 

 

 

 

 

 

limit (A062) to maximum

 

 

 

 

 

 

 

 

frequency (A004).

 

 

 

 

 

 

 

 

0.0 setting is disabled

 

 

 

 

 

 

Lim H

0000.0Hz

>0.0 setting is enabled

 

 

 

 

 

A261

Frequency upper limit

Sets a limit on output frequency

 

0.0

 

0.0

Hz

 

setting, 2nd motor

less than the maximum

 

 

 

 

 

 

 

 

frequency (A204).

 

 

 

 

 

 

 

 

Range is from frequency lower

 

 

 

 

 

 

 

 

limit (A262) to maximum

 

 

 

 

 

 

 

 

frequency (A204).

 

 

 

 

 

 

 

 

0.0 setting is disabled

 

 

 

 

 

 

2Lim H

0000.0Hz

>0.0 setting is enabled

 

 

 

 

 

A062

Frequency lower limit setting

Sets a limit on output frequency

 

0.0

 

0.0

Hz

 

 

 

greater than zero.

 

 

 

 

 

 

 

 

Range is start frequency (B082)

 

 

 

 

 

 

 

 

to frequency upper limit (A061)

 

 

 

 

 

 

 

 

0.0 setting is disabled

 

 

 

 

 

 

Lim L

0000.0Hz

>0.0 setting is enabled

 

 

 

 

 

A262

Frequency lower limit

Sets a limit on output frequency

 

0.0

 

0.0

Hz

 

setting, 2nd motor

greater than zero.

 

 

 

 

 

 

 

 

Range is start frequency (B082)

 

 

 

 

 

 

 

 

to frequency upper limit (A261)

 

 

 

 

 

 

 

 

0.0 setting is disabled

 

 

 

 

 

 

2Lim L

0000.0Hz

>0.0 setting is enabled

 

 

 

 

 

 

 

 

 

 

 

 

Page 94
Image 94
Hitachi X200 Series instruction manual Frequency-related Functions, 2Lim H 0000.0Hz, 2Lim L 0000.0Hz