Hitachi X200 Series Func Name, Settings, 03…ModBus network input, 03… ModBus network input

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 232
Image 232

B5

6.Inverter Parameter Setup - The inverter has several settings related to ModBus communications. The table below lists them together. The Required column indicates which parameters must be set properly to allow communications. You may need to refer to the host computer documentation in order to match some of its settings.

Func.

Name

Required

Settings

Code

 

 

 

A001

Frequency source setting

 

00Keypad potentiometer

 

 

9

01Control terminal

 

 

02Function F001 setting

 

 

 

03ModBus network input

 

 

 

10Calculate function output

A002

Run command source setting

9

01Control terminal

 

 

02Run key on keypad, or digital operator

 

 

 

03ModBus network input

B089

Monitor display select for

 

01Output frequency monitor

 

networked inverter

 

02Output current monitor

 

 

 

03Rotation direction monitor

 

 

04Process variable (PV), PID feedback

 

 

monitor

 

 

 

 

 

 

05Intelligent input terminal status

 

 

 

06Intelligent output terminal status

 

 

 

07Scaled output frequency monitor

C070

Selection of OPE/ModBus

9

02...OPE or option

 

 

03...ModBus (485)

 

 

 

C071

Communication speed selection

9

044800 bps

 

 

059600 bps

 

 

 

0619200 bps

C072

Node allocation

9

Network address, range is 1 to 32

C074

Communication parity selection

9

00No parity

 

 

01Even parity

 

 

 

02Odd parity

C075

Communication stop bit selection

9

Range is 1 to 2

C076

Communication error select

 

00Trip (Error code E60)

 

 

 

01Decelerate to a stop and trip (Error code

 

 

E60)

 

 

02Disable

 

 

 

 

 

 

03Free run stop (coasting)

 

 

 

04Decelerate to a stop

C077

Communication error time-out

Comm. Watchdog timer period,

 

 

range is 0.00 to 99.99 sec.

 

 

 

C078

Communication wait time

9

Time the inverter waits after receiving a

 

 

message before it transmits.

 

 

 

Range is 0. to 1000. ms

NOTE: When you edit and store any of the parameters above, the inverter causes it to take effect immediately. ModBus transmission occurs only after you set the OPE/485 DIP switch to the “485” position and turn on the inverter again. Note that parameters C070 to C078 cannot be changed via the network. To edit them, you must disconnect the inverter from the ModBus and wait for about 30sec until the inverter’s internal keypad begin functioning. Then use this keypad to edit the parameters. Please don’t connect other external programming devices to RJ45 connector, because the bus mode is in RS485 mode. It may cause the inverter or external programming devices to be damaged when DIP switch is in “485” position.

Appendix B

Page 232
Image 232
Hitachi X200 Series instruction manual Func Name, Settings, 03…ModBus network input, 03… ModBus network input