Trip History and Inverter Status

We recommend that you first find the cause of the fault before clearing it. When a fault occurs, the inverter stores important performance data at the moment of the fault. To access the data, use the monitor functions (Dxxx) and select D081 for details about the present fault (En). The previous two faults are stored in D082 and D083, with D(En-1 and En-2). Each error shifts D081–D082 to D082–D083, and writes the new error to D081.

The following Monitor Menu map shows how to access the error codes. When fault(s) exist, you can review their details by first selecting the proper function: D081 is the most recent, and D083 is the oldest.

Monitor Menu

 

1

2

 

2

1

2

1

 

FUNC

 

 

 

 

 

No error

Error

 

No

FUNC

 

 

exists?

 

 

 

Yes

 

 

 

2

 

Trip Conditions

 

 

 

Error Code

1

2

 

 

 

 

 

Output frequency

 

 

 

at trip point

1

2

 

 

 

 

 

Motor current

 

 

 

at trip point

1

2

 

 

 

 

 

DC bus voltage

 

 

 

at trip point

1

2

 

 

 

 

 

Cumulative inverter

 

 

 

operation time at trip point

1

2

 

 

 

 

 

Cumulative power-ON time

 

 

 

at trip point

1

 

 

 

 

 

 

FUNC

Troubleshooting and Maintenance

Page 210
Image 210
Hitachi X200 Series instruction manual Trip History and Inverter Status, Trip Conditions