Terminal Dimensions and Torque Specs

Inverter Mounting and installation

The terminal screw dimensions for all X200 inverters are listed in table below. This information is useful in sizing spade lug or ring lug connectors for wire terminations.

WARNING: Fasten the screws with the specified fastening torque in the table below. Check for any loosening of screws. Otherwise, there is the danger of fire.

 

 

Models 002S~004S,

Models 007S~022S,

 

 

 

Number

007N~022N,037L,

 

 

 

002N~004N

 

 

Connector

of Screw

004H~040H

 

 

 

 

 

 

 

Terminals

Screw

Width

Screw

Width

 

 

 

 

Diameter

(mm)

Diameter

(mm)

 

 

Power Terminals

5

M3.5

7.1

M4

9.2

 

 

(Top side)

 

 

 

 

 

 

 

Power Terminals

8(dual in row)

M3.5

7.1

 

 

(Bottom side)

7

M4

9.2

 

 

Control Signal

15

M2

M2

 

 

Alarm Signal

3

M3

M3

 

 

When connecting wiring, use the tightening torque listed in the following table to safely attach wiring to the connectors.

Screw

Tightening Torque

Screw

Tightening Torque

Screw

Tightening Torque

M2

0.2Nm (max. 0.25 Nm)

M3.5

0.8Nm (max. 0.9 Nm)

M5

2.0Nm (max. 2.2 Nm)

M3

0.5Nm (max. 0.6 Nm)

M4

1.2Nm (max. 1.3 Nm)

Wire the Inverter Input to a Supply

6 Step 6: In this step, you will connect wiring to the input of the inverter. First, you must determine whether the inverter model you have required three-phase power only, or single-phase power only. All models have the same power connection terminals [R/L1], [S/L2], and [T/L3]. So you must refer to the specifications label (on the side of the inverter) for the acceptable power source types! For inverters that can accept single- phase power and are connected that way, terminal [S/L2] will remain unconnected.

The wiring example to the right shows an X200 inverter wired for 3-phase input. Note the use of ring lug connectors for a secure connection.

Input wiring for single-phase input (-SFEF and -NFU models)

Input wiring for 3-phase input (models -NFU, -HFEF, -HFU)

CAUTION: Power terminal assignment is different compared to old models such as L100, L200 series, etc,. Pay attention when wiring the power cable