Two Stage Acceleration and Deceleration

When terminal [2CH] is turned ON, the inverter changes the rate of acceleration and deceleration from the initial settings (F002 and F003) to use the second set of acceleration/ deceleration values. When the terminal is turned OFF, the inverter is returned to the original acceleration and deceleration time (F002 acceleration time 1, and F003 deceleration time 1). Use A092 (acceleration time 2) and A0093 (deceleration time 2) to set the second stage acceleration and deceleration times.

Target frequency

Output

 

 

second

 

initial

frequency

 

[2CH]

1

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

[FW,RV]

1

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

t

In the graph shown above, the [2CH] becomes active during the initial acceleration. This causes the inverter to switch from using acceleration 1 (F002) to acceleration 2 (A092).

Option

Terminal

Function Name

State

Description

Code

Symbol

 

 

 

09

2CH

Two-stage Accelera-

ON

Frequency output uses 2nd-stage acceleration and

 

 

tion and Deceleration

 

deceleration values

 

 

 

OFF

Frequency output uses the initial acceleration 1

 

 

 

 

and deceleration 1 values

Valid for inputs:

C001~C005

Required settings

A092, A093, A094=00

Notes:

 

Function A094 selects the method for second stage acceleration. It must be set = 00 to select the input terminal method in order for the [2CH] terminal assignment to operate.

Example (default input configuration shown—see page 3–49):

2CH

 

 

 

 

 

 

 

5

4

3

2

1

L

PCS

P24

 

- FU models

 

 

 

 

Operations and

Monitoring

See I/O specs on page 4–6.

Page 156
Image 156
Hitachi X200 Series Two Stage Acceleration and Deceleration, Option Terminal Function Name, A092, A093, A094=00