B36

The following table lists the holding registers for the “C” Group Intelligent Input Functions.

List of Holding Registers

 

Func.

Name

R/W

Description

Network Data

 

 

Code

Reg.

Range

Res.

 

 

 

 

 

 

 

C001

Terminal [1] function

R/W

 

1103h

0, 1, 2, 3,

 

 

C201

Terminal [1] function,

R/W

 

1532h

4, 5, 6, 7,

 

 

 

 

2nd motor

 

 

 

8, 9, 11,

 

 

 

C002

Terminal [2] function

R/W

 

1104h

12, 13,

 

 

 

 

 

 

 

 

15, 16,

 

 

 

C202

Terminal [2] function,

R/W

 

1533h

 

 

 

 

18, 19,

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

 

20, 21,

 

 

 

C003

Terminal [3] function

R/W

 

1105h

 

 

 

See “Input Terminal Configuration”

22, 23,

 

 

 

 

 

 

 

 

 

 

C203

Terminal [3] function,

R/W

1534h

24, 27,

 

 

 

 

2nd motor

 

on page 3-49

 

28, 29,

 

 

 

 

 

 

 

 

 

 

C004

Terminal [4] function

R/W

 

1106h

31, 50,

 

 

 

 

 

 

 

 

51, 52,

 

 

 

C204

Terminal [4] function,

R/W

 

1535h

 

 

 

 

2nd motor

 

 

 

53, 64,

 

 

 

C005

Terminal [5] function

R/W

 

1107h

255

 

 

 

 

 

 

 

 

 

 

 

 

C205

Terminal [5] function,

R/W

 

1536h

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

C011

Terminal [1] active state

R/W

Select logic conversion, two option

110Bh

0, 1

 

 

C012

Terminal [2] active state

R/W

codes:

110Ch

0, 1

 

 

C013

Terminal [3] active state

R/W

00normally open [NO]

110Dh

0, 1

 

 

C014

Terminal [4] active state

R/W

01normally closed [NC]

110Eh

0, 1

 

 

C015

Terminal [5] active state

R/W

 

110Fh

0, 1

 

 

C021

Terminal [11] function

R/W

 

1114h

0, 1, 2, 3,

 

 

 

 

 

See “Output Terminal

 

4, 5, 6, 7,

 

 

 

C026

Alarm relay terminal

R/W

Configuration” on page 3-54

1119h

8, 9, 10,

 

 

 

function

 

 

 

43

 

 

 

C028

[AM] signal selection

R/W

Two available functions:

111Bh

0, 1

 

 

 

 

 

00motor speed

 

 

 

 

 

 

 

 

01motor current

 

 

 

 

 

C031

Terminal [11] active

R/W

Select logic conversion:

111Dh

0, 1

 

 

 

state

 

00normally open [NO]

 

 

 

 

 

 

 

 

01normally closed [NC]

 

 

 

 

 

C036

Alarm relay active state

R/W

Select logic conversion:

1122h

0, 1

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

 

 

01normally closed [NC]

 

 

 

 

 

C038

Output mode of low load

R/W

Three option codes:

1178h

0, 1, 2

 

 

 

detection signal

 

00Disabled

 

 

 

 

 

 

 

 

01During acceleration,

 

 

 

 

 

 

 

 

deceleration and constant speed

 

 

 

 

 

 

 

 

02During constant speed only

 

 

 

 

 

C039

Low load detection level

R/W

Set the level of low load detection,

1179h

0 to

0.01%

 

 

 

 

 

range is 0.0 to 2.0*rated current

 

20000

 

 

 

 

 

 

 

 

 

 

 

 

C041

Overload level setting

R/W

Sets the overload signal level

1124h

0 to

0.01%

 

 

 

 

 

between 0% and 200% (from 0 to two

 

20000

 

 

 

 

 

 

time the rated current of the

 

 

 

 

 

C241

Overload level setting,

R/W

153Ah

 

 

 

 

 

2nd motor

 

inverter)

 

 

 

 

 

C042

Frequency arrival

R/W

Sets the frequency arrival setting

1126h

0 to 4000

0.1 Hz

 

 

 

setting for acceleration

 

threshold for the output frequency

 

*1

 

 

 

 

 

 

during acceleration,

 

 

 

 

 

 

 

 

range is 0.0 to 400.0 Hz

 

 

 

 

 

C043

Frequency arrival

R/W

Sets the frequency arrival setting

1128h

0 to 4000

0.1 Hz

 

 

 

setting for deceleration

 

threshold for the output frequency

 

 

 

 

 

 

 

 

during deceleration,

 

 

 

 

 

 

 

 

range is 0.0 to 400.0 Hz

 

 

 

 

Appendix B

Page 263
Image 263
Hitachi X200 Series instruction manual See Input Terminal Configuration