Second Acceleration and Deceleration Functions

The X200 inverter features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape. You can specify the frequency transition point, the point at which the standard acceleration (F002) or deceleration (F003) changes to the second acceleration (A092) or deceleration (A093). Or, you can use intelligent input [2CH] to trigger this transition. These profile options are also available for the second motor settings. Select a transition method via A094 as depicted below. Be careful not to confuse the second acceleration/deceleration settings with settings for the second motor!

A094 = 00

Transition via 2CH input

A094 = 01

Transition via freq. level

Output frequency

0

2CH 1 input

0

Accel 2

Accel 1

t

t

Output frequency

A095

0

Accel 2

 

Frequency

Accel 1

transition point

 

t

Configuring Drive Parameters

 

 

 

“A” Function

Run

Defaults

 

Func.

 

Name /

Description

Mode -FE -FU

Units

 

Code

SRW Display

Edit

(EU)

(USA)

 

A092

Acceleration (2) time setting

Duration of 2nd segment of

9

15.00

15.00

sec

 

 

 

 

acceleration, range is:

 

 

 

 

 

 

ACC 2

0015.00s

0.01 to 3000 sec.

 

 

 

 

 

A292

Acceleration (2) time setting,

Duration of 2nd segment of

9

15.00

15.00

sec

 

 

2nd motor

 

acceleration, 2nd motor, range is:

 

 

 

 

 

 

2ACC2

0015.00s

0.01 to 3000 sec.

 

 

 

 

 

A093

Deceleration (2) time setting

Duration of 2nd segment of

9

15.00

15.00

sec

 

 

 

 

deceleration, range is:

 

 

 

 

 

 

DEC 2

0015.00s

0.01 to 3000 sec.

 

 

 

 

 

A293

Deceleration (2) time setting,

Duration of 2nd segment of

9

15.00

15.00

sec

 

 

2nd motor

 

deceleration, 2nd motor, range is:

 

 

 

 

 

 

 

 

0.01 to 3000 sec.

 

 

 

 

 

 

2DEC2

0015.00s

 

 

 

 

 

A094

Select method to switch to

Two options for switching from

 

00

00

 

 

Acc2/Dec2 profile

1st to 2nd accel/decel:

 

 

 

 

 

 

 

 

002CH input from terminal

 

 

 

 

 

 

ACC CHG

TM

01Transition frequency

 

 

 

 

 

A294

Select method to switch to

Two options for switching from

 

00

00

 

 

Acc2/Dec2 profile, 2nd motor

1st to 2nd accel/decel:

 

 

 

 

 

 

 

 

002CH input from terminal

 

 

 

 

 

 

 

 

01Transition frequency

 

 

 

 

 

 

 

 

(2nd motor)

 

 

 

 

 

 

2ACCCHG

TM

 

 

 

 

 

 

 

 

 

 

 