Multi-speed and Jog Frequency Setting

The X200 inverter has the capability to store and output up to 16 preset frequencies to the motor (A020 to A035). As in traditional motion terminology, we call this multi-speed profile capability. These preset frequencies are selected by means of digital inputs to the inverter. The inverter applies the current acceleration or deceleration setting to change from the current output frequency to the new one. The first multi-speed setting is duplicated for the second motor settings (the remaining 15 multi-speeds apply only to the first motor).

The jog speed setting is used whenever the Jog command is active. The jog speed setting range is arbitrarily limited to 10 Hz, to provide safety during manual operation. The acceleration to the jog frequency is instantaneous, but you can choose from three modes for the best method for stopping the jog operation.

 

 

 

“A” Function

 

Run

 

Defaults

 

 

Func.

Name /

 

Description

Mode -FE -FU

Units

 

 

Code

SRW Display

 

Edit

(EU)

 

(USA)

 

 

A020

Multi-speed frequency setting

Defines the first speed of a multi-

9

0.0

 

0.0

Hz

 

 

 

 

 

speed profile, range is 0.0 / start

 

 

 

 

 

 

 

 

 

 

frequency to 400Hz

 

 

 

 

 

 

 

 

SPD 00s

0000.0Hz

A020

= Speed 0 (1st motor)

 

 

 

 

 

 

 

A220

Multi-speed frequency

Defines the first speed of a multi-

9

0.0

 

0.0

Hz

 

 

 

setting, 2nd motor

speed profile or a 2nd motor,

 

 

 

 

 

 

 

 

 

 

range is 0.0 / start frequency to

 

 

 

 

 

 

 

 

 

 

400Hz

 

 

 

 

 

 

 

 

2SPD00s

0000.0Hz

A220

= Speed 0 (2nd motor)

 

 

 

 

 

 

 

A021

Multi-speed frequency

Defines 15 more speeds,

9

See

 

See

Hz

 

 

to

settings

 

range is 0.0 / start frequency to

 

next

 

next

 

 

 

A035

(for both motors)

 

400 Hz.

 

row

 

row

 

 

 

 

 

 

A021=Speed 1 ~ A035=Speed15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPD 01s

000.0Hz

A021

 

 

0.0

 

0.0

 

 

 

 

SPD 02s

000.0Hz

A022

 

 

0.0

 

0.0

 

 

 

 

SPD 03s

000.0Hz

A023

 

 

0.0

 

0.0

 

 

 

 

SPD 04s

000.0Hz

A024

 

 

0.0

 

0.0

 

 

 

 

SPD 05s

000.0Hz

A025

 

 

0.0

 

0.0

 

 

 

 

SPD 06s

000.0Hz

A026

 

 

0.0

 

0.0

 

 

 

 

SPD 07s

000.0Hz

A027

 

 

0.0

 

0.0

 

 

 

 

SPD 08s

000.0Hz

A028

 

 

0.0

 

0.0

 

 

 

 

SPD 09s

000.0Hz

A029

 

 

0.0

 

0.0

 

 

 

 

SPD 10s

000.0Hz

A030

 

 

0.0

 

0.0

 

 

 

 

SPD 11s

000.0Hz

A031

 

 

0.0

 

0.0

 

 

 

 

SPD 12s

000.0Hz

 

 

 

 

 

 

 

SPD 13s

000.0Hz

A032

 

 

0.0

 

0.0

 

 

 

 

SPD 14s

000.0Hz

A033

 

 

0.0

 

0.0

 

 

 

 

SPD 15s

000.0Hz

A034

 

 

0.0

 

0.0

 

 

 

 

 

 

A035

 

 

0.0

 

0.0

 

 

 

A038

Jog frequency setting

Defines limited speed for jog,

9

1.00

 

1.00

Hz

 

 

 

 

 

range is 0.00 / start frequency to

 

 

 

 

 

 

 

 

Jog-F

001.00Hz

9.99 Hz

 

 

 

 

 

 

 

A039

Jog stop mode

 

Define how end of jog stops the

 

00

 

00

 

 

 

 

 

motor; three options:

 

 

 

 

 

 

 

 

 

 

00Free-run stop

 

 

 

 

 

 

 

 

 

 

01Controlled deceleration

 

 

 

 

 

 

 

 

Jog-Mode

FRS

02DC braking to stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive Parameters

Page 89
Image 89
Hitachi X200 Series instruction manual Multi-speed and Jog Frequency Setting, Frs