B34

List of Holding Registers

 

Func.

Name

R/W

Description

Network Data

 

 

 

Code

Reg.

Range

 

Res.

 

 

 

 

 

 

 

 

B086

Frequency scaling

R/W

Specify a constant to scale the displayed

10D5h

1 to 999

 

0.1

 

 

 

conversion factor

 

frequency for D007 monitor, range is 0.1

 

 

 

 

 

 

 

 

 

to 99.9

 

 

 

 

 

 

B087

STOP key enable

R/W

Select whether the STOP key on the

10D6h

0, 1

 

 

 

 

 

 

keypad is enabled,

 

 

 

 

 

 

 

 

 

two option codes:

 

 

 

 

 

 

 

 

 

00Enabled

 

 

 

 

 

 

 

 

 

01Disabled

 

 

 

 

 

 

B088

Restart mode after

R/W

Selects how the inverter resumes

10D7h

0, 1

 

 

 

 

FRS

 

operation with free-run stop (FRS) is

 

 

 

 

 

 

 

 

 

cancelled, two options:

 

 

 

 

 

 

 

 

 

00Restart from 0Hz

 

 

 

 

 

 

 

 

 

01Restart from frequency detected

 

 

 

 

 

 

 

 

 

from real speed of motor (frequency

 

 

 

 

 

 

 

 

 

matching)

 

 

 

 

 

 

B089

Monitor display

R/W

Selects the parameter displayed on the

10D8h

1 to 7

 

 

 

 

select for networked

 

keypad display when the inverter is

 

 

 

 

 

 

 

inverter

 

networked, 7 options:

 

 

 

 

 

 

 

 

 

01Output frequency monitor

 

 

 

 

 

 

 

 

 

02Output current monitor

 

 

 

 

 

 

 

 

 

03Rotation direction monitor

 

 

 

 

 

 

 

 

 

04Process variable (PV), PID feedback

 

 

 

 

 

 

 

 

 

monitor

 

 

 

 

 

 

 

 

 

05Intelligent input terminal status

 

 

 

 

 

 

 

 

 

06Intelligent output terminal status

 

 

 

 

 

 

 

 

 

07Scaled output frequency monitor

 

 

 

 

 

 

B091

Stop mode selection

R/W

Select how the inverter stops the motor,

10DAh

0, 1

 

 

 

 

 

 

two option codes:

 

 

 

 

 

 

 

 

 

00DEC (decelerate to stop)

 

 

 

 

 

 

 

 

 

01FRS (free run to stop)

 

 

 

 

 

 

B092

Cooling fan control

R/W

Selects when the fan is ON per inverter

10DBh

0, 1, 2

 

 

 

 

 

 

operation, three options:

 

 

 

 

 

 

 

 

 

00Fan is always ON

 

 

 

 

 

 

 

 

 

01Fan is ON during run, OFF during

 

 

 

 

 

 

 

 

 

stop (5 min. delay from ON to OFF)

 

 

 

 

 

 

 

 

 

02Fan is temperature controlled

 

 

 

 

 

 

B130

Over-voltage

R/W

Pauses deceleration ramp when DC bus

10F5h

0, 1

 

 

 

 

LADSTOP enable

 

voltage rises above threshold level, in

 

 

 

 

 

 

 

 

 

order to avoid over-voltage trip.

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

 

01Enable

 

 

 

 

 

 

B131

Over-voltage

R/W

Sets the threshold level for over-voltage

10F6h

330 to 395,

 

1 V

 

 

 

LADSTOP level

 

LADSTOP. When the DC bus voltage is

 

660 to 790

 

 

 

 

 

 

 

above the threshold value, the inverter

 

 

 

 

 

 

 

 

 

stops deceleration until the DC bus

 

 

 

 

 

 

 

 

 

voltage is less than the threshold setting

 

 

 

 

 

 

 

 

 

again. Two voltage ranges with 1V

 

 

 

 

 

 

 

 

 

resolution:

 

 

 

 

 

 

 

 

 

330 to 395V (200V class)

 

 

 

 

 

 

 

 

 

660 to 790V (400V class)

 

 

 

 

 