Automatic Voltage Regulation (AVR) Function

The automatic voltage regulation (AVR) feature keeps the inverter output waveform at a relatively constant amplitude during power input fluctuations. This can be useful if the installation is subject to input voltage fluctuations. However, the inverter cannot boost its motor output to a voltage higher than the power input voltage. If you enable this feature, be sure to select the proper voltage class setting for your motor.

 

 

“A” Function

Run

Defaults

Func.

Name /

 

Description

Mode -FE -FU

Units

Code

SRW Display

Edit (EU)

 

(USA)

A081

AVR function select

 

Automatic (output) voltage

 

00

 

00

 

 

 

regulation, selects from three

 

 

 

 

 

 

 

 

type of AVR functions, three

 

 

 

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

00AVR enabled

 

 

 

 

 

 

 

 

01AVR disabled

 

 

 

 

 

 

 

 

02AVR enabled except during

 

 

 

 

 

 

AVR Mode

ON

deceleration

 

 

 

 

 

A082

AVR voltage select

 

200V class inverter settings:

 

230/

 

230/

V

 

 

 

……200/215/220/230/240

 

400

 

460

 

 

 

 

400V class inverter settings:

 

 

 

 

 

 

AVR AC

00230V

……380/400/415/440/460/480

 

 

 

 

 