Frequency Arrival Signals

Operations and Monitoring

The Frequency Arrival group of outputs help coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F001). Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility. For example, you can have an output turn ON at one frequency during acceleration, and have it turn OFF at a different frequency during deceleration. All transitions have hysteresis to avoid output chatter if the output frequency is near one of the thresholds.

 

Option

 

Terminal

Function Name

State

 

Description

 

 

 

 

Code

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

 

FA1

Frequency Arrival

ON

when output to motor is at the set frequency

 

 

 

 

Type 1 – Constant

OFF

when output to motor is OFF, or in any

 

 

 

 

Speed

 

acceleration or deceleration ramp

 

 

 

 

02

 

FA2

Frequency Arrival

ON

when output to motor is at or above the set

 

 

 

 

Type 2 – Over

 

frequency thresholds for, even if in acceleration or

 

 

 

 

frequency

 

deceleration ramps

 

 

 

 

 

 

 

 

OFF

when output to motor is OFF, or during

 

 

 

 

 

 

acceleration or deceleration before the respective

 

 

 

 

 

 

thresholds are crossed

 

 

 

 

Valid for inputs:

11, AL0 – AL2

 

Example for terminal [11] (default output

 

Required settings

(none)

 

configuration shown – see page 3-54):

 

Notes:

 

 

 

Inverter output

 

 

 

 

For most applications you will need to use only

 

 

 

 

terminal circuit

FA1

 

one type of frequency arrival outputs (see

 

 

 

 

 

 

 

 

examples). However, it is possible assign both

 

 

 

 

 

 

 

output terminals to output functions [FA1] and

 

 

 

 

 

 

 

[FA2].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CM2

11

 

 

 

 

 

 

 

 

 

For each frequency arrival threshold, the output anticipates the threshold (turns ON early) by 1.5Hz.

The output turns OFF as the output frequency

 

 

 

 

 

RY

 

 

 

 

 

 

 

 

 

 

 

moves away from the threshold, delayed by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5Hz.

Example for terminal [AL0], [AL1], [AL2] (requires

The delay time of the output signal is 60 ms

output configuration – see page 54):

(nominal).

 

 

 

 

 

 

 

 

 

 

 

The example circuit for terminal [11] drives a

Inverter logic

 

FA1

relay coil. Note the use of a diode to prevent the

circuit board

 

 

 

 

 

 

 

negative going turn-off spike generated by the

 

 

 

 

 

 

 

 

 

 

 

coil from damaging the inverter’s output

 

 

 

 

 

 

 

 

 

 

 

transistor.

 

 

 

 

 

 

 

 

 

 

 

 

 

AL0

 

AL1

AL2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See I/O specs on page 4-6