Configuring Drive Parameters

351

Input Function Summary Table – This table shows all thirty-one intelligent input functions at a glance. Detailed description of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4-8.

Input Function Summary Table

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

00

FW

FORWARD Run/Stop

ON

Inverter is in Run Mode, motor runs forward

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

01

RV

Reverse Run/Stop

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

02

CF1 *1

Multi-speed Select,

ON

Binary encoded speed select, Bit 0, logical 1

 

 

 

 

Bit 0 (LSB)

OFF

Binary encoded speed select, Bit 0, logical 0

 

 

03

CF2

Multi-speed Select,

ON

Binary encoded speed select, Bit 1, logical 1

 

 

 

 

Bit 1

OFF

Binary encoded speed select, Bit 1, logical 0

 

 

04

CF3

Multi-speed Select,

ON

Binary encoded speed select, Bit 2, logical 1

 

 

 

 

Bit 2

OFF

Binary encoded speed select, Bit 2, logical 0

 

 

05

CF4

Multi-speed Select,

ON

Binary encoded speed select, Bit 3, logical 1

 

 

 

 

Bit 3 (MSB)

OFF

Binary encoded speed select, Bit 3, logical 0

 

 

06

JG

jogging

ON

Inverter is in Run Mode, output to motor runs

 

 

 

 

 

 

at jog parameter frequency

 

 

 

 

 

OFF

Inverter is in Stop Mode

 

 

07

DB

External DC braking

ON

DC braking will be applied during deceleration

 

 

 

 

 

OFF

DC braking will not be applied

 

 

08

SET

Set (select) 2nd Motor

ON

The inverter uses 2nd motor parameters for

 

 

 

 

Data

 

generating frequency output to motor

 

 

 

 

 

OFF

The inverter uses 1st (main) motor parameters

 

 

 

 

 

 

for generating frequency output to motor

 

 

09

2CH

2-stage Acceleration

ON

Frequency output uses 2nd-stage acceleration

 

 

 

 

and Deceleration

 

and deceleration values

 

 

 

 

 

OFF

Frequency output uses standard acceleration

 

 

 

 

 

 

and deceleration values

 

 

11

FRS

Free-run Stop

ON

Causes output to turn OFF, allowing motor to

 

 

 

 

 

 

free run (coast) to stop

 

 

 

 

 

OFF

Output operates normally, so controlled

 

 

 

 

 

 

deceleration stop motor

 

 

12

EXT

External Trip

ON

When assigned input transitions OFF to ON,

 

 

 

 

 

 

inverter latches trip event and displays E12

 

 

 

 

 

OFF

No trip event for ON to OFF, any recorded trip

 

 

 

 

 

 

events remain in history until reset

 

 

13

USP

Unattended Start

ON

On powerup, the inverter will not resume a Run

 

 

 

 

Protection

 

command (mostly used in the US)

 

 

 

 

 

OFF

On powerup, the inverter will resume a Run

 

 

 

 

 

 

command that was active before power loss

 

 

15

SFT

Software Lock

ON

The keypad and remote programming devices

 

 

 

 

 

 

are prevented from changing parameters

 

 

 

 

 

OFF

The parameters may be edited and stored

 

 

16

AT

Analog Input

ON

Refer to “Analog Input Settings” on page 3-13.

 

 

 

 

Voltage/Current Select

OFF

 

 

 

18

RS

Reset Inverter

ON

The trip condition is reset, the motor output is

 

 

 

 

 

 

turned OFF, and powerup reset is asserted

 

 

 

 

 

OFF

Normal power-ON operation

 

Page 125
Image 125
Hitachi X200 Series instruction manual 51, Input Function Summary Table Option, Function Name Description