433

Terminal

Default setting

Safety Stop switch condition

Safety Stop switch

Safety Stop switch

Safety Stop switch

Number

S8 = OFF

S8 = ON

S8 = ON Æ OFF

 

1

FW

FW

FW

 

 

 

 

2

RV

RV

RV

 

 

 

 

3

CF1

EMR

- (No func.)

[HW based for 1b input]

 

 

 

4

CF2 [US ver. :USP]

RS

RS

[HW based for 1a input]

[Normal 1a]

 

 

5

RS

- (No func.)

- (No func.)

(PTC assignable)

 

 

 

This means that terminal 5 will be “no function” when S8 is made ON. So if you want to use the terminal 5 with a specific function under the switch S8 is turned ON, you need to assign manually. Additionally the terminal 3 will also change to no function when the switch S8 is made OFF again.

Please pay attention not to change the switch S8 needlessly. Otherwise there will be an unexpected performance of your system.

Option

Terminal

Function Name

State

Description

Code

Symbol

 

 

 

64

EMR

Safety Stop

ON

Emergency signal is activated

 

 

 

OFF

Emergency signal is not activated

Operations

Valid for inputs:

C001~C005

Required settings

Notes:

Both active state (normally open or normally close) setting of EMR and EXT must be the same setting.

Example (default input configuration shown—see page 3–49):

 

RS EMR

 

 

 

 

 

5

4

3

2

1

L

PCS

P24

and Monitoring

See I/O specs on page 4–6.

NOTE: In any case the total system (including the inverter unit) must comply to EN60204-1 (safety of machinery) and other norms that are required. Refer to each norm that is required on your system.

Page 172
Image 172
Hitachi X200 Series instruction manual 33, Required settings