Input Function Summary Table

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

19

PTC

PTC thermistor

ANLG

When a thermistor is connected to terminal [5]

 

 

 

 

Thermal Protection

 

and [L], the inverter checks for over-temperature

 

 

 

 

 

 

and will cause trip event and turn OFF output to

 

 

 

 

 

 

motor

 

 

 

 

 

OPEN

A disconnect of the thermistor causes a trip

 

 

 

 

 

 

event, and the inverter turns OFF the motor

 

 

20

STA

Start

ON

Starts the motor rotation

 

 

 

 

(3-wire interface)

OFF

No change to present motor status

 

 

21

STP

Stop

ON

Stops the motor rotation

 

 

 

 

(3-wire interface)

OFF

No change to present motor status

 

 

22

F/R

FWD, REV

ON

Selects the direction of motor rotation: ON =

 

 

 

 

(3-wire interface)

 

FWD. While the motor is rotating, a change of

 

 

 

 

 

 

F/R will start a deceleration, followed by a

 

 

 

 

 

 

change in direction

 

 

 

 

 

OFF

Selects the direction of motor rotation: OFF =

 

 

 

 

 

 

REV. While the motor is rotating, a change of F/R

 

 

 

 

 

 

will start a deceleration, followed by a change in

 

 

 

 

 

 

direction

 

 

23

PID

PID Disable

ON

Temporarily disables PID loop control. Inverter

 

 

 

 

 

 

output turns OFF as long as PID Enable is active

 

 

 

 

 

 

(A071=01)

 

 

 

 

 

OFF

Has no effect on PID loop operation, which

 

 

 

 

 

 

operates normally if PID Enable is active

 

 

 

 

 

 

(A071=01)

 

 

24

PIDC

PID Reset

ON

Resets the PID loop controller. The main

 

 

 

 

 

 

consequence is that the integrator sum is forced

 

 

 

 

 

 

to zero

 

 

 

 

 

OFF

No effect on PID controller

 

 

27

UP

Remote Control UP

ON

Accelerates (increases output frequency) motor

 

 

 

 

Function (motorized

 

from current frequency

 

 

 

 

speed pot.)

OFF

Output to motor operates normally

 

 

28

DWN

Remote Control Down

ON

Decelerates (decreases output frequency) motor

 

 

 

 

Function (motorized

 

from current frequency

 

 

 

 

speed pot.)

OFF

Output to motor operates normally

 

 

29

UDC

Remote Control Data

ON

Clears the UP/DWN frequency memory by

 

 

 

 

Clearing

 

forcing it to equal the set frequency parameter

 

 

 

 

 

 

F001. Setting C101 must be set=00 to enable this

 

 

 

 

 

 

function to work

 

 

 

 

 

OFF

UP/DWN frequency memory is not changed

 

 

31

OPE

Operator Control

ON

Forces the source of the output frequency setting

 

 

 

 

 

 

A001 and the source of the Run command A002

 

 

 

 

 

 

to be from the digital operator

 

 

 

 

 

OFF

Source of output frequency set by A001 and

 

 

 

 

 

 

source of Run command set by A002 is used

 

Configuring Drive Parameters