B089: Monitor display select for networked inverter – When the X200 inverter is controlled via network, the inverter’s keypad display can still provide Monitor Mode. The D00x parameter selected by function B089 sill be displayed on the keypad. See “Local Monitoring During Network Operation” on page 3-8for more details.

B092: Cooling Fan Control – You can select the performance of the cooling fan (if your inverter has the fan) whether it stops or keep on running, after the inverter stops the motor. This can result in an additional energy saving.

 

 

“B” Function

Run

 

Defaults

Func.

Name /

 

Description

Mode

-FE

 

-FU

Units

Code

SRW Display

 

Edit

(EU)

 

(USA)

B089

Monitor display select for

Selects the parameter displayed on the

9

01

 

01

 

networked inverter

 

keypad display when the inverter is

 

 

 

 

 

 

 

 

networked, 7 options:

 

 

 

 

 

 

 

 

01Output frequency monitor

 

 

 

 

 

 

 

 

02Output current monitor

 

 

 

 

 

 

 

 

03Rotation direction monitor

 

 

 

 

 

 

 

 

04Process variable (PV), PID

 

 

 

 

 

 

 

 

feedback monitor

 

 

 

 

 

 

 

 

05Intelligent input terminal status

 

 

 

 

 

 

 

 

06Intelligent output terminal status

 

 

 

 

 

 

PANEL

d001

07Scaled output frequency monitor

 

 

 

 

 

B092

Cooling fan control

 

Selects when the fan is ON per inverter

 

00

 

00

 

 

 

operation, three options:

 

 

 

 

 

 

 

 

00Fan is always ON

 

 

 

 

 

 

 

 

01Fan is ON during run, OFF during

 

 

 

 

 

 

FAN-CTRL

OFF

stop (5 min. delay from ON to OFF)

 

 

 

 

 

 

 

 

02Fan is temperature controlled

 

 

 

 

 