Set Second Motor, Special Set

Operations and Monitoring

If you assign the [SET] function to an intelligent input terminal, you can select between two sets of motor parameters. The second parameters store an alternate set of motor characteristics. When the terminal [SET] is turned ON, the inverter will use the second set of parameters to generate the frequency output to the motor. When changing the state of the [SET] input terminal, the change will not take effect until the inverter is stopped. Special Set [SP-SET] is for changing the second motor parameters without stopping the motor. However the changeable parameters are limited.

When you turn ON the [SET] input, the inverter operates per the second set of parameters. When the terminal is turned OFF, the output function returns to the original settings (first set of motor parameters). Refer to “Configuring the Inverter for Multiple Motors” on page 4–58for details.

 

Parameters

SET

SP-SET

 

Parameters

 

SET

SP-SET

 

 

F002/F202

9

9

 

A093/A293

9

9

 

 

F003/F203

9

9

 

A094/A294

9

9

 

 

A001/A201

9

-

 

A095/A295

9

9

 

 

A002/A202

9

-

 

A096/A296

9

9

 

 

A003/A203

9

-

 

b012/b212

9

-

 

 

A004/A204

9

-

 

b013/b213

9

-

 

 

A020/A220

9

9

 

b021/b221

9

-

 

 

A041/A241

9

-

 

b022/b222

9

-

 

 

A042/A242

9

9

 

b023/b223

9

-

 

 

A043/A243

9

9

 

b028/b228

9

-

 

 

A044/A244

9

-

 

C001~C005/

9

-

 

 

A045/A245

9

-

 

C201~C205

 

 

 

 

 

 

 

 

A061/A261

9

9

 

C041/C241

9

-

 

 

A062/A262

9

9

 

H003/H203

9

-

 

 

A092/A292

9

9

 

H004/H204

9

-

 

 

 

 

 

 

 

H006/H206

9

-

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

Terminal

 

Function Name

State

 

 

 

Description

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

53

SET

SP-SET

Set (select) 2nd Motor data

Set 2nd motor data Special SET

ON

causes the inverter to use the 2nd set of motor

 

parameters for generating the frequency output to

 

motor

OFF

causes the inverter to use the 1st (main) set of

 

motor parameters for generating the frequency

 

output to motor

Valid for inputs:

C001~C005

Required settings

(none)

Notes:

 

If the terminal state is changed while the inverter is running, the inverter continues using the current set of parameters until the inverter is stopped.

Example (requires input configuration—see page 3–49):

SET / SP-SET