Overload Advance Notice Signal

When the output current exceeds a preset value, the [OL] terminal signal turns ON. The parameter C041 sets the overload threshold. The overload detection circuit operates during powered motor operation and during regenerative braking. The output circuits use open-collector transistors, and are active low.

Output current

C041

C041

[OL] 1 signal 0

Threshold

Power running

Regeneration

Threshold

ON

ON

t

Operations and Monitoring

Option

Terminal

Function Name

 

State

 

 

 

 

 

Description

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

OL

Overload Advance

 

ON

 

when output current is more than the set

 

 

Notice Signal

 

 

 

threshold for the overload signal

 

 

 

 

OFF

 

when output current is less than the set threshold

 

 

 

 

 

 

for the overload signal

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

11, AL0 – AL2

 

 

Example for terminal [11] (default output

Required settings

C041

 

 

configuration shown – see page 3-35):

Notes:

 

 

 

 

 

Inverter output

 

 

 

 

 

 

 

 

 

 

 

The default value is 100%. To change the level

 

terminal circuit

 

 

 

 

OL

from the default, set C041 (overload level).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The accuracy of this function is the same as the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

function of the output current monitor on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[FM] terminal (see “Analog Output Operation”

 

 

 

 

CM2

 

 

 

 

 

11

 

 

on page 4–55).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The example circuit for terminal [11] drives a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relay coil. Note the use of a diode to prevent the

 

 

 

 

 

 

 

 

RY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

negativegoing turn-off spike generated by the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

coil from damaging the inverter’s output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transistor.

 

 

 

 

Example for terminal [AL0], [AL1], [AL2] (requires

 

 

 

 

 

 

 

 

 

 

 

 

output configuration – see page 4-35 and 3-54):

 

 

 

 

 

 

Inverter logic

 

OL

 

 

 

 

 

 

circuit board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL0

 

AL1

AL2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See I/O specs on page 4-6