Analog Input Current/Voltage Select

The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input terminals for external frequency control. When intelligent input [AT] is ON, you can set the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency. Note that you must also set parameter A001 = 01 to enable the analog terminal set for controlling the inverter frequency.

Option

Terminal

Function Name

State

Description

Code

Symbol

 

 

 

16

AT

Analog Input

ON

See the table down below

 

 

Voltage/Current

OFF

 

 

 

Select

 

 

Operations and Monitoring

Valid for inputs:

C001~C005

Required settings

A001 = 01

Notes:

 

If the [AT] option is not assigned to any intelligent input terminal, then inverter recognizes [AT] = OFF in following table.

Be sure to set the frequency source setting A001=01 to select the analog input terminals.

Example (default input configuration shown for –FU models; –FE models require input configuration—see page 3–49):

AT

5 4 3 2 1 L PCS P24

AM H O OI L

Å 4-20 mA

+ -

0-10 V

See I/O specs on page 4–6.

Combination of A005 setting and [AT] input for analog input activation.

A005

[AT] Input

Analog Input Configuration

02

ON

Keypad Pot

OFF

[O]

 

03

ON

Keypad Pot

OFF

[OI]

 

04

(ignored)

[O]

05

(ignored)

[OI]

Note that you cannot give [O] and [OI] input at the same time on X200 inverter.