xiv

Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in the tables below.

Input

Motor Output

 

 

 

Power Terminal

 

Torque

 

 

 

Inverter Model

Wiring Size

 

 

 

Voltage

kW

HP

 

 

Ft-lbs

(N-m)

 

 

 

Range (AWG)

 

 

 

 

 

 

 

 

 

 

 

0.2

1/4

 

X200-002SFE/NFU

 

 

0.6

0.8

 

0.4

1/2

 

X200-004SFE/NFU

14

 

 

 

 

 

 

 

 

0.55

3/4

 

X200-005SFE

(75°C only)

 

 

 

 

0.75

1

 

X200-007SFE/NFU

 

 

 

 

 

200V

1.1

1 1/2

 

X200-011SFE

12

 

0.9

1.2

Class

1.5

2

 

X200-015SFE/NFU

 

 

 

 

 

 

 

 

 

 

 

2.2

3

 

X200-022SFE/NFU

10

 

 

 

 

 

3.7

5

 

X200-037LFU

12

 

0.9

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.4

1/2

 

X200-004HFE/HFU

 

 

 

 

 

 

0.75

1

 

X200-007HFE/HFU

16

 

 

 

 

 

1.5

2

 

X200-015HFE/HFU

 

 

0.9

1.2

400V

2.2

3

 

X200-022HFE/HFU

14

 

 

 

 

 

 

Class

3.0

4

 

X200-030HFE

 

 

 

 

 

(60°C only)

 

 

 

 

4.0

5

 

X200-040HFE/HFU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connector

 

Wiring Size

Torque

 

 

 

 

Range (AWG)

Ft-lbs

(N-m)

 

 

 

 

 

 

 

Logic and Analog connectors

 

30 – 16

0.16 – 0.19

0.22 – 0.25

 

Relay connector

 

 

 

30 – 14

0.37 – 0.44

0.5 – 0.6

 

Wire Connectors

WARNING: Field wiring connections must be made by a UL Listed and CSA certified ring lug terminal connector sized for the wire gauge being used. The connector must be fixed using the crimping tool specified by the connector manufacturer.

Terminal (ring lug)

Cable support

Cable

Page 15
Image 15