Getting started

Inverter Output to the Motor

The AC motor must be connected only to the inverter’s

3-phase AC motor

 

 

 

 

 

 

 

 

 

output terminals. The output terminals are uniquely

 

 

 

 

 

 

 

 

U/T1

labeled (to differentiate them from the input terminals)

 

 

 

 

 

 

 

 

 

with the designations U/T1, V/T2, and W/T3. this

 

 

 

 

 

 

 

 

 

corresponds to typical motor lead connection designations

 

 

 

 

 

 

 

 

 

T1, T2, and T3. It is not often necessary to connect a

 

 

 

 

 

 

 

 

 

particular motor lead for a new application. The

 

 

 

 

 

 

 

 

 

consequence of swapping any two of the three connections is

W/T3

 

 

 

 

 

 

 

V/T2

 

 

 

 

 

 

 

the reversal of the motor direction. In applications where

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reversed rotation could cause equipment damage or

 

Earth GND

personnel injury, be sure to verify direction of rotation

 

 

 

 

 

 

 

 

 

before attempting full-speed operation.

 

 

 

 

 

 

 

 

 

For safety to personnel, you must connect the motor chassis ground to the ground connection at the bottom of the inverter housing.

Notice the three connections to the motor do not include one marked “Neutral” or “Return”. The motor represents a balanced “Y” impedance of the inverter, so there is no need for a separate return. In other words, each of the three “Hot” connections serves also as a return for the other connections of their phase relationship.

The Hitachi inverter is a rugged and reliable device. The intention is for the inverter to assure the role of controlling power to the motor during all normal operations. Therefore, this manual instruct you not to switch off power to the inverter while the motor is running (unless it is an emergency stop). Also, do not install or use disconnect switches in the wiring from the inverter to the motor (except thermal disconnect). Of course, safety-related devices such as fuses must be in the design to break power during a malfunction, as required by NEC and local codes.