311

Run Command Source Setting – For parameter A002, the following table provides a further description of each option, and a reference to other page(s) for more information.

Code

Run Command Source

Refer to page(s)…

01

Control terminal – The [FW] or [RV] input terminals control

4-11

 

Run/Stop operation

 

02

Keypad Run key – The Run and Stop keys provide control

2-24

03

ModBus network input – The network has a dedicated coil

B-19

 

for Run/Stop command and a coil for FW/RV

 

A001/A002 Override Sources – The inverter allows some sources to override the setting for output frequency and Run command in A001 and A002. this provides flexibility for applications that occasionally need to use a different source, leaving the standard settings in A001/A002.

The inverter has other control sources that can temporarily override the parameter A001 setting, forcing a different output frequency source. The following table lists all frequency source setting methods and their relative priority (“1” is the highest priority).

Priority

A001 Frequency Source Setting Method

Refer to page…

1

[CF1] to [CF4] Multi-speed terminals

4-12

2

[OPE] Operator Control intelligent input

4-29

3

[F-TM] intelligent input

4-31

4

[AT] terminal

4-22

5

A001 Frequency source setting

3-10

Configuring Drive Parameters

The inverter also has other control sources that can temporarily override the parameter A002 setting, forcing a different Run command source. The following table lists all Run command setting methods and their relative priority (“1” is the highest priority).

Priority

A002 Run Command Setting Method

Refer to page…

1

[OPE] Operator Control intelligent input

4-29

2

[F-TM] intelligent input

4-31

3

A002 Run command source setting

3-10

Page 85
Image 85
Hitachi X200 Series instruction manual Code Run Command Source, A001 Frequency Source Setting Method Refer to page…