Network Communications Settings

The following table lists parameters that configure the inverter’s serial communications port. The settings affect how the inverter communication with a digital operator (such as SRW-0EX), as well as a ModBus network (for networked inverter applications). The settings cannot be edited via the network, in order to ensure network reliability. Refer to “ModBus Network Communications” on page B-1for more information on controlling any monitoring your inverter from a network.

 

 

“C” Function

Run

Defaults

Func.

Name /

Description

Mode -FE -FU

Units

Code

SRW Display

Edit (EU)

 

(USA)

C070

Selection of OPE / ModBus

Two option codes:

 

02

 

02

 

 

 

02OPE or option

 

 

 

 

 

 

PARAM

REM

03ModBus (485)

 

 

 

 

 

C071

Communication speed

Three option codes:

 

06

 

04

baud

 

selection

 

044800 bps

 

 

 

 

 

 

 

 

059600 bps

 

 

 

 

 

 

COM BAU

4800

0619200 bps

 

 

 

 

 

C072

Node allocation

 

Set the address of the inverter on

 

1.

 

1.

 

 

 

the network. Range is 1 to 32

 

 

 

 

 

 

COM ADR

00001

 

 

 

 

 

 

 

 

 

 

 

 

C074

Communication parity

Three option codes:

 

00

 

00

 

selection

 

00No parity

 

 

 

 

 

 

 

 

01Even parity

 

 

 

 

 

 

 

 

02Odd parity

 

 

 

 

 

 

COM PRTY

NON

 

 

 

 

 

 

 

 

 

 

 

 

C075

Communication stop bit

Range is 1 to 2

 

1

 

1

bit

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM STP

1BIT

 

 

 

 

 

 

C076

Communication error select

Selects inverter response to

 

02

 

02

 

 

 

communications error.

 

 

 

 

 

 

 

 

Five options:

 

 

 

 

 

 

 

 

00Trip (Error code E60)

 

 

 

 

 

 

 

 

01Decelerate to a stop and trip

 

 

 

 

 

 

 

 

(Error code E60)

 

 

 

 

 

 

 

 

02Disable

 

 

 

 

 

 

 

 

03Free run stop (coasting)

 

 

 

 

 

 

COM ESlct

None

 

 

 

 

 

 

04Decelerate to a stop

 

 

 

 

 

C077

Communication error time-

Sets the communications watchdog

 

0.00

 

0.00

sec.

 

out

 

timer period.

 

 

 

 

 

 

COM ETIM

000.00s

Range is 0.00 to 99.99 sec

 

 

 

 

 

C078

Communication wait time

Time the inverter waits after

 

0.

 

0.

msec.

 

 

 

receiving a message before it

 

 

 

 

 

 

 

 

transmits.

 

 

 

 

 

 

COM Wait

00000ms

Range is 0. to 1000. ms

 

 

 

 

 

Configuring Drive Parameters

Page 134
Image 134