Configuring Drive Parameters

 

 

 

 

 

 

 

 

 

359

 

 

 

 

 

 

 

 

 

 

 

 

 

“C” Function

Run

Defaults

 

Func.

Name /

Description

Mode -FE -FU

Units

 

Code

SRW Display

Edit (EU)

 

(USA)

 

C041

Overload level setting

Sets the overload signal level

 

Rated current

A

 

 

 

 

between 0% and 200% (from 0 to

 

for each

 

 

 

 

 

two time the rated current of the

 

inverter model

 

 

 

OV LVL

001.60A

 

 

 

inverter)

 

 

 

 

 

 

 

C241

Overload level setting,

Sets the overload signal level

 

Rated current

A

 

 

2nd motor

 

between 0% and 200% (from 0 to

 

for each

 

 

 

 

 

two time the rated current of the

 

inverter model

 

 

 

2OV LVL

001.60A

inverter)

 

 

 

 

 

 

 

C042

Frequency arrival setting

Sets the frequency arrival setting

 

0.0

 

0.0

 

Hz

 

 

for acceleration

threshold for the output frequency

 

 

 

 

 

 

 

 

 

 

during acceleration,

 

 

 

 

 

 

 

 

ARV ACC

0000.0Hz

range is 0.0 to 400.0 Hz

 

 

 

 

 

 

 

C043

Frequency arrival setting

Sets the frequency arrival setting

 

0.0

 

0.0

 

Hz

 

 

for deceleration

threshold for the output frequency

 

 

 

 

 

 

 

 

 

 

during deceleration,

 

 

 

 

 

 

 

 

ARV DEC

0000.0Hz

range is 0.0 to 400.0 Hz

 

 

 

 

 

 

 

C044

PID deviation level setting

Sets the allowable PID loop error

 

3.0

 

3.0

 

%

 

 

 

 

magnitude (absolute value), SP-PV,

 

 

 

 

 

 

 

 

ARV PID

003.0%

range is 0.0 to 100%

 

 

 

 

 

 

 

C052

PID FBV function high

When the PV exceeds this value,

 

100.0

100.0

%

 

 

limit

 

the PID loop turns OFF the PID

 

 

 

 

 

 

 

 

 

 

second stage output, range is 0.0 to

 

 

 

 

 

 

 

 

PID LtU

0100.0%

 

 

 

 

 

 

 

 

100%

 

 

 

 

 

 

 

C053

PID FBV function variable

When the PV goes below this

 

0.0

 

0.0

 

%

 

 

low limit

 

value, the PID loop turns ON the

 

 

 

 

 

 

 

 

 

 

PID second stage output, range is

 

 

 

 

 

 

 

 

PID LtL

0000.0%

0.0 to 100%

 

 

 

 

 

 

 

Page 133
Image 133
Hitachi X200 Series instruction manual 59