B10

Explanation of function codes

Read Coil Status [01h]:

This function reads the status (ON/OFF) of selected coils. An example follows below.

Read intelligent input terminals [1] to [5] of an inverter having a slave address “8.”

Appendix B

This example assumes the intelligent input terminals have terminal states listed below.

Item

 

 

Data

 

 

Intelligent input

[1]

[2]

[3]

[4]

[5]

terminal

 

 

 

 

 

Coil number

7

8

9

10

11

Coil Status

ON

OFF

ON

OFF

OFF

Query:

No.

Field Name

Example

(Hex)

 

 

1

Slave address *1

08

2

Function code

01

3

Coil start address *4

00

 

(high order)

 

4

Coil start address *4

06

 

(low order)

 

5

Number of coils

00

 

(high order *2)

 

6

Number of coils

05

 

(low order *2)

 

7

CRC-16 (high order)

1C

8

CRC-16 (low order)

91

Response:

No.

Field Name

Example

(Hex)

 

 

 

1

Slave address

08

2

Function code

01

3

Data size (in bytes)

01

 

 

 

4

Coil data *3

05

 

 

 

 

5

CRC-16

(high order)

92

 

 

 

 

6

CRC-16

(low order)

17

 

 

 

 

Note 1: Broadcasting is disabled.

Note 2: When 0 or more than 31 is specified as a number of coils, error code “03h” is returned.

Note 3: Data is transferred by the specified number of data bytes (data size).

Note 4: The PDU Coils are addressed starting at zero. Therefore coils numbered 1-31 are addressed as 0-30. Coil address value (transmitted on Modbus line) is 1 less than the Coil Number.

The data set in the response shows terminal state of coils 7 to 14.

Data “05h = 00000101b” indicates the following assuming coil 7 is the LSB.

Item

 

 

 

Data

 

 

 

Coil Number

14

13

12

11

10

9

8

7

Coil Status

OFF

OFF

OFF

OFF

OFF

ON

OFF

ON

When a read coil is outside the defined coils, the final coil data to be transmitted contains “0“as the status of the coil outside the range.

When the Read Coil Status command cannot be executed normally, see the exception response.

Page 237