Network Detection Signal (Integrated ModBus)

Inverter Mounting and installation

The Network Detection Signal output indicates the general status of network communications (integrated ModBus communication). The inverter has a programmable watchdog timer to monitor network activity. Parameter C077 sets the time-out period. If communications stop or pause longer than the specified time-out period, the NDc output turns ON.

Option

Terminal

Function Name

State

Description

 

Code

Symbol

 

 

 

 

 

08

NDc

Network

ON

when the communication watchdog timer (period

 

 

Disconnection

 

specified by C077) has timed out.

 

 

Signal (ModBus)

OFF

when the communication watchdog timer is

 

 

 

 

satisfied by regular communications activity

Valid for inputs:

11, AL0 – AL2

 

Example for terminal [11] (default output

Required settings

C076, C077

 

configuration shown – see page 3-54):

Notes:

 

 

 

Inverter output

 

 

 

 

 

 

To disable the communications watchdog timer,

terminal circuit

NDc

set C077=00.00 sec.

 

 

 

If you set Communications Error Select to “Disable” (C076=02), you still have the option of

using the Network Detection Signal and setting

CM2

 

11

 

the watchdog time-out period with C077.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example for terminal [AL0], [AL1], [AL2] (requires output configuration – see page 4-35 and 3-54):

Inverter logic

 

 

NDc

circuit board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AL0

 

AL1

AL2

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See I/O specs on page 4-6

Additionally, the inverter can respond to a communications time-out in various ways. Refer to the following diagram (top of next page). You configure the desired response via function C076, Communications Error Select. This selects whether or not you want the inverter to trip (alarm with error code E60) and whether to stop the motor or just let it coast. Together, parameters C076 and C077 set the network detection watchdog time- out and the inverter’s response.