Hitachi X200 Series instruction manual 33

Models: X200 Series

1 286
Download 286 pages 46.11 Kb
Page 72
Image 72

233

Set the Number of Motor Poles – The motor’s internal winding arrangement determines its number of magnetic poles. The specification label on the motor usually indicates the number of poles. For proper operation, verify the parameter setting matches the motor poles. Many industrial motors have four poles, corresponding to the default setting in the inverter (H004).

Follow the steps in the table below to verify the motor poles setting and change if necessary (the table resumes action from the end of the previous table.)

 

 

Action

Display

 

Func./Parameter

(Starting point)

 

 

 

 

 

 

b012

 

Level of electronic thermal setting

 

 

 

 

 

 

 

 

 

 

 

 

 

FUNC

 

 

 

 

 

 

Press the

key.

 

b- - -

 

“B” Group selected

 

 

 

 

 

 

 

Press the

 

key two times.

 

 

 

“H” Group selected

1

 

H- - -

 

 

 

 

 

 

 

 

Press the

FUNC

key.

 

 

 

First “H” Group parameter

 

H003

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

key once

 

H004

 

Motor poles parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

= 2 poles

 

FUNC

 

 

 

 

4

= 4 poles (default)

Press the

key.

 

4

 

 

 

6

= 6 poles

 

 

 

 

 

 

 

 

 

 

 

 

8

= 8 poles

 

 

 

 

 

 

Set to your motor specs (your display

Press the

1

or 2 key as needed.

 

4

 

 

 

may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Store parameter, returns to “H”

Press the

STR

key.

 

H004

 

 

 

Group list

 

 

 

 

 

 

This step concludes the parameter setups for the inverter. You are almost ready to run the motor for the first time!

TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then study the “Keypad Navigation Map on page 2-26to determine the current state of the keypad controls and display. As long as you do not press the STR key, no parameter will be changed by keypad entry errors. Note that power cycling the inverter causes it to power up Monitor Mode, displaying the value for D001 (output frequency).

The next section will show you how to monitor a particular parameter from the display. Then you will be ready to run the motor.

Inverter Mounting and installation

Page 72
Image 72
Hitachi X200 Series instruction manual 33