B7

Data:

A function command is set here.

The data format used in the X200 series is corresponding to the Modbus data format below.

Name of Data

Description

Coil

Binary data that can be referenced and changed ( 1 bit long)

Holding Register

16-bit data that can be referenced and changed

Function code:

Specify a function you want to make the inverter execute. Function codes available to the X200 series are listed below.

 

 

 

Maximum data size

Maximum number of

 

Function Code

Function

(bytes available

data elements available

 

 

 

per message)

per message

Appendix B

0 1 h

Read Coil Status

4

0 3 h

Read Holding Resistor

4

0 5 h

Write in Coil

1

0 6 h

Write in Holding Register

1

0 8 h

Loopback Test

0 F h

Write in Coils

4

1 0 h

Write in Registers

4

 

 

 

32 coils (in bits)

4 registers (in bytes)

1 coil (in bits)

1 register (in bytes)

32 coils (in bits)

4 registers (in bytes)

Error check:

Modbus-RTU uses CRC (Cyclic Redundancy Check) for error checking.

The CRC code is 16-bit data that is generated for 8-bit blocks of arbitrary length.

The CRC code is generated by a generator polynomial CRC-16 (X16+ X15+ X2+ 1).

Header and trailer (silent interval):

Latency is the time between the reception of a query from the master and transmission of a response from the inverter.

3.5 characters (24 bits) are always required for latency time. If the latency time shorter than 3.5 characters, the inverter returns no response.

The actual transmission latency time is the sum of silent interval (3.5 characters long) + C078 (transmission latency time).

Page 234