B20

Appendix B

List of Coil Numbers

 

Coil

Name

R/W

Description

 

 

Number

 

 

 

 

 

 

 

0014h

Alarm signal

R

0…Normal

 

 

 

 

 

1…Trip

 

 

0015h

PID deviation signal

R

0…OFF

 

 

0016h

Overload signal

R

1…ON

 

 

0017h

Frequency arrival signal

R

 

 

 

 

(set frequency or above)

 

 

 

 

0018h

Frequency arrival signal

R

 

 

 

 

(at constant speed)

 

 

 

 

0019h

Run Mode signal

R

 

 

 

001Ah

Data writing

R

0…Normal status

 

 

 

 

 

1…Writing

 

 

001Bh

CRC error

R

0…No error *2

 

 

001Ch

Overrun error

R

1…Error

 

 

001Dh

Framing error

R

 

 

 

001Eh

Parity error

R

 

 

 

001Fh

Check sum error

R

 

 

Note 1: ON usually when either the control circuit terminal board or a coil is ON. Among control circuit terminal board (intelligent input terminals) and coils, the control circuit terminal board has a high priority. If the master cannot reset the coil ON status due to a transmission line break, please turn ON and OFF the control circuit terminal board to make the coil to OFF status.

Note 2: The content of a transmission error is held until the error is reset. (The error can be reset while the inverter is running.)

Page 247
Image 247
Hitachi X200 Series instruction manual …Off