DC Bus AVR for deceleration Settings

This function is to achieve stable DC bus voltage in case of deceleration. DC bus voltage raises due to regeneration during deceleration. When this function is activated (B133=01), inverter controls the deceleration time so that the DC bus voltage not to go up to the overvoltage trip level, and leads to the tripless operation during deceleration.

Please note that the actual deceleration time may be longer in this case.

DC bus voltage

Threshold voltage to start DC bus AVR (B134)

t

Freq

 

 

 

t

 

 

 

 

Normal

DC bus AVR

operation

 

 

 

 

“B” Function

Run

Defaults

 

 

Func.

 

Name /

Description

Mode -FE -FU

Units

 

 

Code

SRW Display

Edit (EU)

 

(USA)

 

 

B055

DC bus AVR for decel.

Proportional gain adjustment for

 

0.2

 

0.2

 

 

 

P-gain

 

DC bus AVR function. Range is:

 

 

 

 

 

 

 

 

 

 

0.2 to 5.0

 

 

 

 

 

 

 

 

VpnP

0000.2s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B056

DC bus AVR for decel.

Integration time adjustment for

 

0.2

 

0.2

sec

 

 

 

I-time

 

DC bus AVR function. Range is:

 

 

 

 

 

 

 

 

 

 

0.0 to 150.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VpnI

0000.2s

 

 

 

 

 

 

 

 

B057

DC bus AVR for decel.

Derivative time adjustment for

 

0.0

 

0.0

sec

 

 

 

D-time

 

DC bus AVR function. Range is:

 

 

 

 

 

 

 

 

 

 

0.0 to 100.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VpnD

0000.2s

 

 

 

 

 

 

 

 

B133

DC bus AVR selection

00Disabled

 

00

 

00

 

 

 

 

 

01Enabled

 

 

 

 

 

 

 

 

Vpn AVR

OFF

 

 

 

 

 

 

 

 

B134

Threshold voltage of DC bus

Setting of threshold voltage of

 

380

 

380

V

 

 

 

AVR setting

DC bus voltage to start DC bus

 

/760

 

/760

 

 

 

 

 

 

AVR function. Range is:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V class330 to 395

 

 

 

 

 

 

 

 

 

 

400V class660 to 790

 

 

 

 

 

 

 

 

Vpn LVL

00380V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring Drive Parameters

Page 120
Image 120