350

The input logic conversion is programmable for each of the six inputs default to normally open (active high), but you can select normally closed (active low) in order to invert the sense of the logic.

 

 

“C” Function

Run

 

Defaults

Func.

Name /

 

Description

Mode

-FE

 

-FU

Units

Code

SRW Display

 

Edit

(EU)

 

(USA)

C011

Terminal [1] active state

Select logic conversion, two option

 

00

 

00

 

 

 

codes:

 

 

 

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

O/C-1

NO

01normally closed [NC]

 

 

 

 

 

C012

Terminal [2] active state

Select logic conversion, two option

 

00

 

00

 

 

 

codes:

 

 

 

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

O/C-2

NO

01normally closed [NC]

 

 

 

 

 

C013

Terminal [3] active state

Select logic conversion, two option

 

00

 

00

 

 

 

codes:

 

 

 

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

O/C-3

NO

01normally closed [NC]

 

 

 

 

 

C014

Terminal [4] active state

Select logic conversion, two option

 

00

 

01

 

 

 

codes:

 

 

 

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

O/C-4

NC

01normally closed [NC]

 

 

 

 

 

C015

Terminal [5] active state

Select logic conversion, two option

 

00

 

00

 

 

 

codes:

 

 

 

 

 

 

 

 

00normally open [NO]

 

 

 

 

 

 

O/C-5

NO

01normally closed [NC]

 

 

 

 

 

NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.

Intelligent Input Terminal Overview

Each of the five intelligent terminals may be assigned any of the options in the following table. When you program one of the option codes for terminal assignments C001 to C005, the respective terminal assumes the function role of that option code. The terminal functions have a symbol or abbreviation that we use to label a terminal using that function. For example, the “Forward Run” command is [FW]. The physical label on the terminal block connector is simply 1, 2, 3, 4, or 5. However, schematic examples in this manual also use the terminal symbol (such as [FW]) to show the assigned option. The option codes for C011 to C015 determines the active state of the logical input (active high or active low).

Configuring Drive Parameters

Page 124
Image 124
Hitachi X200 Series instruction manual 50, Intelligent Input Terminal Overview