Configuring Drive Parameters

349

“C” Group: Intelligent Terminal Functions

The five input terminals [1], [2], [3], [4], and [5] can be configured for any of 31 different functions. The next two tables show how to configure the five terminals. The inputs are logical, in that they are either OFF or ON. We define these states as OFF=0, and ON=1.

The inverter comes with default options for the five terminals. These settings are initially unique, each one having its own setting. Note that European and US versions have different default settings. You can use any option on any terminal, and even use the same option twice to create a logical OR (though usually not required).

NOTE: Terminal [5] has the ability to be a logical input, and to be an analog input for a thermistor device when PTC function (option code 19) is assigned to that terminal.

Input Terminal Configuration

Functions and Options – The function codes in the following table let you assign one of twenty eight options to any of the five logic inputs for the X200 inverters. The functions C001 through C005 configure the terminals [1] through [5] respectively. The “value” of these particular parameters is not a scalar value, but it is a discrete number that selects one option from many available options.

For example, if you set function C001=00, you have assigned option 00 (Forward Run) to terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.

 

 

“C” Function

Run

Defaults

Func.

Name /

 

Description

Mode

-FE

-FU

Units

Code

SRW Display

 

Edit

(EU)

(USA)

C001

Terminal [1] function

 

Select input terminal [1] function, 30

 

00

00

 

 

 

options(see next section)

 

[FW]

[FW]

 

 

IN-TM 1

FW

 

 

C201

Terminal [1] function,

 

Select input terminal [1] function for

 

 

 

 

 

2nd motor

 

2nd motor, 30 options(see next

 

 

 

 

 

2IN-TM 1

FW

section)

 

 

 

 

C002

Terminal [2] function

 

Select input terminal [2] function, 30

 

01

01

 

IN-TM 2

RV

options(see next section)

 

[RV]

[RV]

 

C202

Terminal [2] function,

 

Select input terminal [2] function for

 

 

 

 

 

2nd motor

 

2nd motor, 30 options(see next

 

 

 

 

 

2IN-TM 2

RV

section)

 

 

 

 

C003

Terminal [3] function

 

Select input terminal [3] function, 30

 

02

16

 

 

 

options(see next section)

 

[CF1]

[AT]

 

 

IN-TM 3

AT

 

 

C203

Terminal [3] function,

 

Select input terminal [3] function for

 

02

16

 

 

2nd motor

 

2nd motor, 30 options(see next

 

[CF1]

[AT]

 

 

2IN-TM 3

AT

section)

 

 

 

 

C004

Terminal [4] function

 

Select input terminal [4] function, 30

 

03

13

 

 

 

options(see next section)

 

[CF2]

[USP]

 

 

IN-TM 4

USP

 

 

C204

Terminal [4] function,

 

Select input terminal [4] function for

 

 

 

 

 

2nd motor

 

2nd motor, 30 options(see next

 

 

 

 

 

2IN-TM 2

USP

section)

 

 

 

 

C005

Terminal [5] function

 

Select input terminal [5] function, 30

 

18

18

 

 

 

options(see next section)

 

[RS]

[RS]

 

 

IN-TM 5

2CH

 

 

C205

Terminal [5] function,

 

Select input terminal [5] function for

 

 

 

 

 

2nd motor

 

2nd motor, 30 options(see next

 

 

 

 

 

IN-TM 5

2CH

section)

 

 

 

 

Page 123