Ensure Adequate Ventilation

2 Step 2: To summarize the caution messages – you will need to find a solid, non- flammable, vertical surface that is in a relatively clean and dry environment. In order to ensure enough room for air circulation around the inverter to aid in cooling, maintain the specified clearance and the inverter specified in the diagram.

Inverter Mounting and installation

Clear area

10 cm (3.94”)

minimum

 

X200

 

inverter

5 cm (1.97”)

5 cm (1.97”)

minimum

minimum

 

10 cm (3.94”)

 

minimum

Air flow

CAUTION: Be sure to maintain the specified clearance area around the inverter and to provide adequate ventilation. Otherwise, the inverter may overheat and cause equipment damage or fire.

Keep Debris Out of Inverter Vents

3 Step 3: Before proceeding to the wiring section, it’s

 

a good time to temporarily covers the inverter’s

Ventilation holes

ventilation openings. Paper and masking tape are

(top)

all that is needed. This will prevent harmful debris

 

such as wire clippings and metal shavings from

 

entering the inverter during installation.

 

Please observe this checklist while mounting the

 

inverter:

Ventilation holes

 

1. The ambient temperature must be in the range

(both sides)

 

of 10 to 40°C.

 

2.Keep any other heat-producing equipment as far away from the inverter as possible.

3.When installing the inverter in an enclosure, maintain the clearance around the inverter and verify that its ambient is within specification when the enclosure door is closed.

4.Do not remove the front housing at any time during operation.

Page 49
Image 49
Hitachi X200 Series instruction manual Ensure Adequate Ventilation, Keep Debris Out of Inverter Vents